Level Sense Pro Manuale utente

USER MANUAL
www.level-sense.com

Contents
About Level Sense Pro ............................ 1.0
Device Specications ........................ 1.1
Requirements.................................... 1.2
In the Box........................................... 1.3
Status LEDs ........................................ 1.4
Wiring Panel....................................... 1.5
Installation...................................................2.0
Installation Warning.......................... 2.1
Mounting to Pump Discharge Pipe ... 2.2
Mounting to the Wall........................ 2.3
Installing Float Sensor ...................... 2.4
Installing Leak Sensor....................... 2.5
Installing Level Sensor...................... 2.6
Powering On ...............................................3.0
Connect to Wi-Fi........................................4.0
Connect with WPS............................. 4.1
Connect with Hotspot....................... 4.2
Product Registration—Portal..................5.0
Create Portal Account....................... 5.1
Claim Device ...................................... 5.2
Congure Device Name ................... 5.3
Update Frequency............................. 5.4
Alarm Inputs ...............................................6.0
Per Input Type ................................... 6.1 – 6.4
Alarm Outputs............................................7.0
Per Output Type................................ 7.1 – 7.3
Disabling Alarm from Device........... 7.4
Device and Alarm Testing........................8.0
Per Device Testing............................. 8.1 - 8.5
Maintenance ...............................................9.0
Password Reset........................................10.0
Battery Warning........................................11.0
Service Disclaimer....................................12.0
Warranty ....................................................13.0
Test Log........................................................14.0
Troubleshooting ........................................15.0
Support .......................................................16.0

1.0 About Level Sense Pro
Level Sense Pro is a Wi-Fi based residential environmental
monitor designed specically for the home owner who wants to
keep a watchful eye on their property at all times. Level Sense
Pro monitors ve critical elements of the home as alarm inputs—
sustained power loss, sump pit high water level, water leak(s),
temperature and humidity levels.
Each of the ve alarm inputs can be congured individually as
alarm triggers based on their state or level. There are three alarm
outputs of the Level Sense Pro; email/SMS (text message), audible
siren and alarm relay contacts. Additional detail of the alarm
outputs can be found in the alarm outputs section of the manual.
Please read the User Manual carefully before using the Level
Sense Pro.
1.1 Device Specifications
Operating Temperature: 32-122 F° (0-50 C°)
Operating Humidity: 0-95% RH, non-condensing
Input Power: 12VDC 700mA
Battery: 3.7V Lithium Ion Polymer 1100mAH *Read Battery Warning
Siren: 90db *Estimated
Antenna: Internally integrated
Sensor Inputs: 2x Dry contact
Relay Contact: 48VDC 1Amp Max
Dimensions: 5x6x1.25”
Weight: 2lbs
Contains FCC ID: 2AC7Z-ESP8266EX
1.2 Requirements
120 VAC Power outlet
Wi-Fi internet within range of Level Sense
Wi-Fi device with web browsing
Screw Driver, at head #3 or #4
1

1. Level Sense Pro 2. Power Supply
3. Float Switch & Bracket 4. Leak Sensor
5. Level Sensor Wire 6. Accessories
1.3 In the Box
(Optional Accessory)
2

1.4 Status LEDs
The status LEDs on the Level Sense Pro provide a visual indication
of the control state. The below table is a system status guide.
Wiring of sensors (level, leak and oat switch) have no polarity.
To connect sensors, turn the terminal screw counterclockwise to
open the wiring clamp. Insert wire into the clamp and turn
terminal screw clockwise to close clamp on wire.
Tighten until wire is rmly secured.
1.5 Wiring Panel
Color /LED Blue Yellow Red White
Power AC Power
Good
No AC
Power
No AC Power
Low Battery —
Cloud Connected
to Wi-Fi
Flash:
Connecting
Solid: WPS
Mode
Wrong
Password
Or out-of-
range
Hotspot
Mode
Calibrate Calibrated Learning
Level — —
Alarm No Alarms —Active Alarm —
RESET
DC
USER LEVEL
SENSOR
FLOAT
SWITCH
LEAK
SENSOR
ALARM
NC COM NO
3

2.0 Installation
Level Sense Pro is designed for indoor installation only. The ideal
mounting location is in the utility room within a few feet of the
sump pump pit. Consideration should be taken to keep within
range of the homes Wi-Fi router. Wi-Fi range varies based on the
router and environmental conditions. We recommend range
testing before installation. If the device is out of range, consider
a Wi-Fi range extender. The Level Sense Pro can be mounted
in two dierent ways, choose from the following options.
2.1 Installation Warning
Working around water and electricity is inherently dangerous.
Disconnect all electrical circuit breakers near the sump pump and
installation area before beginning work. If you are unfamiliar or
uncomfortable please contact a licensed electrician to perform the
installation.
2.2 Mounting to Pump Discharge Pipe
For most customers, mounting to the discharge pipe of the
sump pump, or other nearby PVC pipe, is the simplest installation
location. First, install the two self-adhesive mounting squares to
the back of the device as shown below. Then, feed a zip tie through
the mounting square opening and around the pipe and zip tight.
Repeat for the second mounting square. Install the device
approximately 1-6 feet above the oor.
TIP: For larger diameter pipes, connect a second zip tie in series to extend
the length of the zip tie.
4

2.3 Mounting to the Wall
The back side of the Level Sense Pro accepts two #6 screws. The
screws are spaced at 3.375” and are mounted horizontally. Install
the device approximately 3-6 feet above the oor.
Mounting Screws
3.375 “
HAVE A QUESTION?
Send us an email: [email protected] or submit a request
through our webpage: http://www.level-sense.com/pages/support
Contact support
or Phone: 515-957-1050
5

2.4 Installing Float Sensor
The oat sensor mounts above the normal pump water line and
detects when the water level has reached a point above normal
operating range.
The oat sensor installs on the sump pump discharge pipe.
Using the provided plastic oat bracket and two zip ties, securely
mount the oat to the discharge pipe. The sliding oat portion of
the sensor should face down. Mount the oat approximately
six (6) inches above the sump pump normal water line. This
level can usually be found by looking at the side walls of the pit to
visually see the high water mark roughly level with the top of the
pump. The wires from the oat sensor connect to the far right
two terminals on the Level Sense Pro. The wires do not have
polarity, and cannot be wired backwards. Do not increase
wire length beyond the length provided.
6

2.5 Installing Leak Sensor (Optional)
The leak sensor monitors for pooling water on a at surface, this
sensor does not need to be installed if this type of monitoring is
not required.
The leak sensor can be mounted near the sump pit or other area
where water would pool in the event of a leak. Typical locations
are near a water heater or HVAC system which could leak during
a malfunction. The sensor needs to be placed at on the oor
with the metal sensing elements down. The sensor must be
submerged in a minimum pool of water 1/8” in depth before
activating. The wires do not have polarity, and cannot be wired
backwards. Do not increase wire length of the leak sensor
beyond the length provided.
7

2.6 Installing Level Sensor (Optional Accessory)
The level sensor is used to help determine pump cycle frequency.
This sensor is not required and only provides an approximation
of water level following a calibration process. This is useful if you
are unsure how often your pump runs. High water alarms are
triggered from the oat sensor.
The level sensor is installed vertically on the PVC discharge pipe of
the sump pump. The sensor wire attaches to the PVC pipe with zip
ties. Place the sealed end of the sensor wire as far down the pipe
as possible. The closer the sealed end of the wire is to the bottom
of the pipe, the more resolution of water level you will see. Care
must be taken to secure the sensor wire to the discharge pipe
to avoid it being sucked into the pump. Also, avoid allowing the
sensor wire to come in contact with the power cable of the sump
pump or metal piping as this can skew the reading. Do not modify
level sensor wire length.
8