Lumel ND25 Manuale utente

ND.25
POWER NETWORK METER
USER’S MANUAL
FOR INTERFACE


Section Contents
1. Introduction
2. Communication Parameter selection screen
2.1 Address Setting
2.2 RS 485 Baud rate
2.3 RS 485 Parity
2.4 Quit Communication Parameters
3. RS 485 ( ModBus ) Output
3.1 Accessing 3X and 4X registers for Reading Measured values
3.2 Accessing 4X register for Reading & Writing Settings
3.3 User Assignable Modbus Registers
4. Datalogging
4.1 Event Based Datalogging
4.2 Time Based Datalogging
4.3 Load Profile Datalogging
5. Connection for RS 485
1

The Multifunction Energy Meter is a panel mounted 96 x 96mm DIN Quadratic Digital Panel Meter, which
measures important electrical parameters in 3 ph 4 wire / 3 wire / 1ph Network and replaces the multiple
analog panel meters. It measures electrical parameters like AC voltage, Current, Frequency, Power, Energy
(Active / Reactive / Apparent), phase angle, power factor,individual harmonics & many more. The instrument
integrates accurate measurement technology (All Voltages & current measurements are True RMS upto 31st
Harmonic) with LCD display with backlit.
It can be configured & Programmed at site for the following :PT Primary, PT Secondary, CT Primary, CT
Secondary , 3 Phase 3W, 3 Phase 4W, 1 Phase 2W system.
The front panel has three push buttons using which the user can scroll through different screens & configure
the product. The front panel also has Impulse red led, flashing at rate proportional to measured power.
Up Key
Enter Key
Down Key
Energy/Counter Screen
Measurement Screen
Load Graphics
Phase Sequence
Indication
Impulse LED
1. Introduction
Operation via standard RS485 is also possible. Through this optional interface all the above mentioned
parameters can be configured and programmed. For modbus service, it is essential that device address, baud rate
and parity should be configured properly.
This document specifies only the interface between a Master device and Meter for electrical variable through
MODBUS over RS485.
2

Press “ ” to enter into edit mode, prompt for first digit. (Flashing digit
indicates cursor position).
Press the “ ” and “ ” keys to scroll the value of the first digit. Press the
“ ” key to advance to next digit.
Similarly, enter second and third digits of address. After entering third digit,
pressing “ ” key confirms the selection and shows “Address Setting”
screen (see Section 3.2.2.1).
2.1 Address Setting
This screen applies to the RS 485 output only. This screen allows the user
to set RS 485 address for the meter.
The allowable range of addresses is 1 to 247.
Press “ ” key to advance to “RS 485 Baud Rate” screen (see Section
2.2) or press the “ ” key to advance to the “Quit Communication
Parameters” screen (see Section 2.4).
2. Communication Parameter Selection Screen
2.2 RS 485 Baud Rate
k
This screen allows the user to set Baud Rate of RS 485 port. The values
displayed on screen are in kbaud.
Pressing “ ” key accepts the present value and advance to the “RS 485
Parity Selection” screen (see Section 2.3) and pressing the “ ” key
accepts the present value and advance to the “Address Setting”
screen(see Section 2.1).
Pressing the “ ” key advances to the “Baud Rate Edit” mode and “ ” &
“ ” keys scrolls the value through 4.8, 9.6, 19.2, 38.4 and 57.6 kbaud.
Pressing the “ ” key sets the value and shows the “RS 485 Baud Rate” screen (see Section 2.2).
While using USB port communication the Configuration must be :
Device address: 001 Baud rate : 57600
Parity : None Stop bit: 1
3

2.3 RS 485 Parity
This screen allows the user to set Parity & number of stop bits of RS 485 port.
Pressing “ ” key accepts the present value and advances to “Quit
Communication Parameters” screen (see section 2.4).
Similarly, pressing “ ” key accepts the present value and advances to
“RS 485 Baud Rate” screen (see section 2.2).
Pressing the “ ” key advances to the “Parity & Stop bit Edit” mode &
keys “ ” and “ ” scrolls the value through:
no 1 : no parity with one stop bit no 2 : no parity with two stop bit
E : even parity with one stop bit odd : odd parity with one stop bit
Pressing “ ” key sets the value and advances to “RS 485 Parity Selection” screen (see Section 2.3).
2.4 Quit Communication Parameters
This screen allows user to exit from system “Communication
Parameter Selection” setup.
Pressing the “ ” key advances to “Communication Parameter Selection”
screen (see Section 2.1).
Similarly, pressing the “ ” key advances to “RS 485 Parity” screen (see
Section 2.3).
Pressing the “ ” key advances to “Communication Parameter Selection ”
screen (see Section 2).
3. RS 485 ( ModBus ) Output :
THE MULTIFUNCTION INSTRUMENT supports MODBUS (RS485) RTU protocol (2-wire ) .
Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained
together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents,
an Earth connection should be made at one point on the network. Loop (ring) topology does not require any
termination load. Line topology may or may not require terminating loads depending on the type and length of
cable used. The impedance of the termination load should match the impedance of the cable and be at both
ends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32 instruments can
be connected in RS485 network. The permissible address range for The Meter is between 1 and 247
for 32 instruments. Broadcast Mode (address 0) is not allowed.
The maximum latency time of a Meter is 300 ms i.e. this is the amount of time that can pass before the first
response character is output.
4

After sending any query through software (of the Master), it must allow 300ms of time to elapse before assuming
that the Meter is not going to respond. If slave does not respond within 300 ms, Master can ignore the previous
query and can issue fresh query to the slave.
16 Presets Multiple Registers Set the content of read / write locations ( 4X )
04 Read input Registers Read content of read only location ( 3X )
Read Holding Registers Read content of read /write location ( 4X )
03
Communication Baud Rate is user selectable from the front panel between 4800,9600,19200,38400,57600 bps.
Function code :
8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit field of the message
4 bytes (32 bits) per parameter.
Floating point format ( to IEEE 754)
Most significant byte first (Alternative least significant byte first)
Format of Data Bytes
2 byte Cyclical Redundancy Check (CRC)
Error Checking Bytes
1 start bit,
8 data bits, least significant bit sent first
1 bit for even/odd parity
1 stop bit if parity is used; 1 or 2 bits if no parity
Byte format
Each byte in RTU mode has following format:
01 Illegal function The function code is not supported by Meter
02 Illegal Data Address Attempt to access an invalid address or an
attempt to read or write part of a floating point value
03 Illegal DataValue Attempt to set a floating point variable to an invalid value
Exception Cases : An exception code will be generated when Meter receives ModBus query with valid parity
& error check but which contains some other error ( e.g. Attempt to set floating point variable to an invalid value)
The response generated will be “Function code” ORed with HEX (80H ). The exception codes are listed below
3.1 Accessing 3X and 4X register for reading measured values:
Two consecutive 16 bit registers represent one parameter. Refer TABLE 1 for the addresses of 3X and 4X
registers used for parameters measured by the instrument. Each parameter is held in the 3X as well as 4X
registers. Modbus Code 04 and 03 are used to access all parameters in 3X and 4X registers respectively.
Example :
To read parameter,
Voltage2 from 3X: Start address = 00 02 Number of registers = 02
Watt2 from 4X: Start address = 00 0E Number of registers = 02
5

Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 40 parameters or less. Exceeding the 40 parameter
limit will cause a ModBus exception code to be returned.
Device
Address
Function
Code
Start Address
High
Start Address
Low
Number of
Registers Hi
Number of
Registers Lo
CRC
Low
CRC
High
01 (Hex) 04 (Hex) 00 (Hex) 02(Hex) 00 (Hex) 02(Hex) 30 (Hex) 0A (Hex)
Query for 3X read:
3X Response: Voltage 2 (219.254V)
Device
Address
Function
Code
Byte
Count
Data Register1
High Byte
CRC
High
01 (Hex) 04 (Hex) 04 (Hex) 43 (Hex) 5B (Hex) 41 (Hex) 21 (Hex) 6F (Hex)
Data Register1
Low Byte
Data Register2
High Byte
Data Register2
Low Byte
9B (Hex)
CRC
Low
Byte Count : Total number of data bytes received.
Query for 4X read:
Device
Address
Function
Code
Start Address
High
Start Address
Low
Number of
Registers Hi
Number of
Registers Lo
CRC
Low
CRC
High
01 (Hex) 03 (Hex) 00 (Hex) 0E(Hex) 00 (Hex) 02(Hex) E0 (Hex) C9 (Hex)
4X Response: Watt2 (2000 W)
Device
Address
Function
Code
Byte
Count
Data Register1
High Byte
CRC
High
01 (Hex) 03 (Hex) 04 (Hex) 44 (Hex) FA (Hex) 00 (Hex) 00 (Hex) CE (Hex)
Data Register1
Low Byte
Data Register2
High Byte
Data Register2
Low Byte
F2 (Hex)
CRC
Low
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low : Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Byte count : No.of Bytes Demanded by user in querry.
6

TABLE 1 : 3 X and 4 X register addresses for measured parameters
Address
(3X)
Address
(4X)
Parameter
Number Parameter
Start Address Hex 3X Start Address Hex 4X
High Byte Low Byte High Byte Low Byte
30001
30003
30005
30007
30009
30011
30013
30015
30017
30019
30021
30023
30025
30027
30029
30031
30033
30035
30037
30039
30041
30043
30045
30047
30049
30051
30053
30055
30057
30059
40001
40003
40005
40007
40009
40011
40013
40015
40017
40019
40021
40023
40025
40027
40029
40031
40033
40035
40037
40039
40041
40043
40045
40047
40049
40051
40053
40055
40057
40059
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
V1
V2
V3
I1
I2
I3
W1
W2
W3
VA1
VA2
VA3
VAR1
VAR2
VAR3
PF1
PF2
PF3
Angle1
Angle2
Angle3
Volt Avg
Volt Sum
Current Avg
Current Sum
Watt Avg
Watt Sum
VA Avg
VA Sum
VAr Avg
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
02
04
06
08
0A
0C
0E
10
12
14
16
18
1A
1C
1E
20
22
24
26
28
2A
2C
2E
30
32
34
36
38
3A
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
02
04
06
08
0A
0C
0E
10
12
14
16
18
1A
1C
1E
20
22
24
26
28
2A
2C
2E
30
32
34
36
38
3A
7

TABLE 1 : Continued...
Address
(3X)
Address
(4X)
Parameter
Number Parameter
Start Address Hex 3X Start Address Hex 4X
High Byte Low Byte High Byte Low Byte
30061
30063
30065
30067
30069
30071
30073
30075
30077
30079
30081
30085
30087
30089
30091
30093
30095
30097
30099
30101
30103
30105
30107
30109
30111
30113
30115
30117
30119
30121
40061
40063
40065
40067
40069
40071
40073
40075
40077
40079
40081
40085
40087
40089
40091
40093
40095
40097
40099
40101
40103
40105
40107
40109
40111
40113
40115
40117
40119
40121
31
32
33
34
35
36
37
38
39
40
41
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
VAr Sum
PF Avg
PF Sum
Phase Angle Avg
Phase Angle Sum
Freq
Wh import
Wh export
VArh Capacitive
VArh Inductive
VAh
kW imp demand
max kW imp demand
kW exp demand
max kW exp demand
kVAr Cap. demand
max kVAr Cap. demand
kVAr Ind. demand
max kVAr Ind. demand
KVA demand
max KVA demand
current demand
max current demand
Wh import Overflow count
Wh Import
Wh export Overflow count
Wh export
VArh Cap. Overflow count
VArh Capacitive
VArh Ind. Overflow count
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
3C
3E
40
42
44
46
48
4A
4C
4E
50
54
56
58
5A
5C
5E
60
62
64
66
68
6A
6C
6E
70
72
74
76
78
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
3C
3E
40
42
44
46
48
4A
4C
4E
50
54
56
58
5A
5C
5E
60
62
64
66
68
6A
6C
6E
70
72
74
76
78
8
Indice
Altri manuali Lumel Strumento di misura

Lumel
Lumel NA6 Manuale utente

Lumel
Lumel ND30PNET Manuale utente

Lumel
Lumel ND10 TYPE Manuale utente

Lumel
Lumel N43 Manuale utente

Lumel
Lumel N31U Manuale utente

Lumel
Lumel N14 Manuale utente

Lumel
Lumel N100 Manuale utente

Lumel
Lumel N30P Manuale utente

Lumel
Lumel NR30IoT Manuale utente

Lumel
Lumel VPS10 Manuale utente

Lumel
Lumel N10 Manuale utente

Lumel
Lumel ND40 Manuale utente

Lumel
Lumel NA6 Manuale utente

Lumel
Lumel NA5PLUS Manuale utente

Lumel
Lumel N32O Manuale utente

Lumel
Lumel KS5 Manuale utente

Lumel
Lumel N20PLUS Manuale utente

Lumel
Lumel N21 Manuale utente

Lumel
Lumel N24S Manuale utente

Lumel
Lumel N27P Manuale utente





















