Pilot Communications PMAC735 Manuale utente

PMAC735 Multifunction Measuring Meter
Installation & Operation Manual
V8.2
ZHUHAI PILOT TECHNOLOGY CO., LTD.

2
Danger and warning!
This device can be installed only by professionals.
The manufacturer shall not be held responsible for any accident caused by the failure to
comply with the instructions in this manual.
Risks of electric shocks, burning, or explosion
This device can be installed and maintained only by qualified people.
Before operating the device, isolate the voltage input and power supply and short-circuit
the secondary windings of all current transformers.
Put all mechanical parts, doors, or covers in their original positions before energizing the
device.
Always supply the device with the correct working voltage during its operation.
Failure to take these preventive measures could cause damage to equipment or injuries to
people.

3
CONTENTS
1. General Information........................................................................................... 6
1.1 Pictures of the main unit ...................................................................................................... 7
1.2 Picture of the extension module........................................................................................... 7
1.3 Type of the extension module .............................................................................................. 8
1.4 Characteristics...................................................................................................................... 9
2. Installation and Connection ............................................................................. 10
2.1 Environment....................................................................................................................... 10
2.2 Dimension .......................................................................................................................... 10
2.3 Description of the main unit terminals................................................................................11
2.4 Description of extension module terminals ....................................................................... 12
2.5 Order information............................................................................................................... 16
2.6 Connection.......................................................................................................................... 17
3. Measuring Capability....................................................................................... 20
3.1 Real-time basic electrical parameters ................................................................................ 20
3.2 Power factor symbols......................................................................................................... 21
3.3 Demand parameters............................................................................................................ 22
3.4 Energy parameters.............................................................................................................. 23
3.5 Harmonic parameters (optional) ........................................................................................ 24
4. Operation ......................................................................................................... 26
4.1 Display and keys ................................................................................................................ 26
4.2 Data query .......................................................................................................................... 27
4.3 Setting................................................................................................................................. 41

4
5. Input/output Characteristics (optional)............................................................. 52
5.1 Status input......................................................................................................................... 52
5.2 Relay output ....................................................................................................................... 53
5.3 Pulse outputs....................................................................................................................... 54
5.4 Analog output..................................................................................................................... 56
6. Alarm System (optional).................................................................................. 59
7. SOE /Event Log (optional)............................................................................ 61
8. Communication Protocol ................................................................................. 62
8.1 Overview............................................................................................................................ 62
8.2 Abnormal response............................................................................................................. 63
8.3 Relay control ...................................................................................................................... 64
8.4 Register reading.................................................................................................................. 65
8.5 Register setting................................................................................................................... 66
8.6 Description of data types.................................................................................................... 67
8.7 Calculation factors.............................................................................................................. 67
8.8 Communication values and actual values.......................................................................... 68
8.9 List of universal data registers ........................................................................................... 69
8.10 List of real-time measured data registers......................................................................... 72
8.11 List of energy data registers ............................................................................................. 75
8.12 List of demand data registers ........................................................................................... 77
8.13 List of harmonic data registers......................................................................................... 80
8.14 List of max./min. real time data register.......................................................................... 81
8.15 List of SOE and time registers ......................................................................................... 84
8.16 List of configuration registers.......................................................................................... 85

5
8.17 List of energy setting registers......................................................................................... 91
8.18 05H command control relays ........................................................................................... 92
9. Maintenance and Trouble Shooting.................................................................. 93
10. Technical Datasheet ....................................................................................... 96

6
1. General Information
PMAC735 is a multi-functional power meter, integrating data acquisition and control into a whole.
It can take the place of numerous meters, relays, transducers, and other components. Besides, it
can be used in electric power systems of various voltage classes.
PMAC735 provides one RS485 communication port, so it can be integrated into any electric
power monitoring system. The management software or other configuration software with which
it is equipped enables the setting to be carried out easily. Furthermore, it provides an optional
PROFIBUS communication port, whose 1.5 M communication speed can fully meet the demand
for obtaining real-time data on the site.
PMAC735 is really a measuring meter based on true effective values, able to carry out accurate
measurement of highly non-linear loads. The complicated sampling technology enables it to
measure true effective values up to the 31st harmonic. The user can read remotely some dozens of
measured values and minimum/maximum values on a display screen or via software.
PMAC735 provides multiple extension modules and advanced software functions to meet the
demands of different sites. Its flexible DI/DO configuration facilitates the design of the user.
PMAC735 adopts connection realized by terminals that can be pulled out and inserted, thus
facilitating on-site wiring and maintenance. Especially for the parts to which current is inputted,
PMAC735 uses lockable fixation connections to prevent dangers that may be caused by
accidental coming off of connections.

7
1.1 Pictures of the main unit
Side view Rear view
1.2 Picture of the extension module
Rear view

8
1.3 Type of the extension module
Product Model Description
PMAC735-A 4 status inputs and 4 relay outputs
PMAC735-B 8 status inputs and 2 relay outputs
PMAC735-E 8 status inputs and 2 pulse outputs
PMAC735-P PROFIBUS communication port
【Notes】
1. Each PMAC735 main unit can be equipped with one extension module at most.
2. Digital input requires external dry contact.
3. The capacity of each relay output node is 250 Vac/5Aor 30 Vdc/5A.
4. For pulse output circuits, refer to the subsequent descriptions.
5. The maximum communication speed of the PROFIBUS port is 1.5 Mbps.
6. Some of the customized extension modules are not included.

9
1.4 Characteristics
The main parameters and characteristics of PMAC735 are as follows:
◆ Up to the 31st harmonic.
◆ Accepting standard CT and PT inputs.
◆ The voltage that can be directly measured is up to 500 V (phase-phase).
◆ Achieving the class-1 measuring accuracy stipulated by IEC 62053, with bidirectional
four-quadrant energy values.
◆ High-accuracy measurement of current and voltage (0.1%) (typical situation).
◆ Measurement of THD and K factor.
◆ Build-in clock.
◆ Demand calculation and maximum recording.
◆ Large high-contrast LCD screen, easy for operating and setting with password lock.
◆ Revisable fixed value alarm and relay functions.
◆ RS485 communication, standard MODBUS protocol (extendible PROFIBUS port)
◆ Operating temperature: -20℃~ +60℃.
◆ One optional programmable 4-20 mAanalog output.
◆ Multiple optional extendible modules, providing flexible on-site combinations.
◆ Optional SOE event log.
◆ Standard pluggable connecting terminals,facilitating on-site installation and maintenance.
◆ Maximum and minimum of instant measurement.

10
2. Installation and Connection
2.1 Environment
1. Storage temperature: -30℃~ +70℃
2. Operating temperature: -20℃~ +60℃
3. Humidity: 5% ~ 90%, non-condensing
2.2 Dimension
Panel size: 96.00×96.00 mm
Installation size: 89.50×89.50 mm
Depth: 65.00 mm (the depth will be increased by 25.00 mm if an extension module is added)
Questo manuale è adatto per i seguenti modelli
4
Indice
Altri manuali Pilot Communications Strumento di misura

Pilot Communications
Pilot Communications SPM32 Manuale utente

Pilot Communications
Pilot Communications PMAC901 Manuale utente

Pilot Communications
Pilot Communications PMAC202 Manuale utente

Pilot Communications
Pilot Communications PM-2104 Manuale utente

Pilot Communications
Pilot Communications PMAC615 Manuale utente

Pilot Communications
Pilot Communications PBAT-Gate Manuale utente

Pilot Communications
Pilot Communications PMAC211 Manuale utente

Pilot Communications
Pilot Communications EGO700 Manuale utente

Pilot Communications
Pilot Communications SPM33 Manuale utente