SMC 3000 Series Master Clock Installation Manual(V2)
Sapling, Inc. 1633 Republic Road Huntingdon Valley, PA 19006 Phone: (215) 322-6063 Fax: (215) 322-8498 www.Sapling-Inc.com
Synchronous Protocol Information
Protocol
Type Correction
Code Hourly
Correction
Duration
Daily
Correction
Time
Daily
Correction
Duration
59 minute correction
Simplex 2310-92XX 57 and 77 series
IBM 57, 62, 77, 82 and 87 series
Cincinnati D10 and D12
Latham SS12 types
Edwards 01
Dukane 24SS series
006
8 seconds
05:57:54
17:57:53
Will correct
hours, minutes,
and seconds.
14 seconds
Dukane 24030,24023,24050, 24060 and
24010 types
National Time & Rauland
Rauland Analog 2460 series
National 010-NNE-SRAX,
010-NNE-SRAXLV,
023-NNE-SRAX,
023-NNE-SRAXLV,
030-NNE-SRAX,
030-NNE-SRAXLV,
060-12E-SRAX,
060-12E-SRAXLV
001 or 002
25 seconds
06:00:00
18:00:00
Will correct
hours, minutes,
and seconds.
001 = 25 seconds
on, 35 seconds
off every minute
for 24 minutes.
002 = 24 minute
closure from
6:00:25 to
6:24:25 AM &
PM
Stromberg E3109 and WS310
003
10 seconds
11:56:00
23:56:00
Will correct
hours, minutes,
and seconds.
45 seconds
National, 010-NNE-SR,
010-NNE-SRLV
023-NNE-SR,
023-NNE-SRLV
030-NNE-SR
030-NNE-SRLV
060-12E-SR
060-12E-SRLV
020
25 seconds
N/A
N/A
Hourly
Correction
Time
xx:57:54
Will correct
the minutes
and
seconds.
xx:00:00
Will correct
the minutes
and seconds.
xx:56:05
Will correct
the minutes
and seconds.
xx:00:00
Dukane 24BF209, 24BF212 707-8 and
707-9 types
005
xx:57:03
Will correct
the minutes
and seconds.
xx:58:05
57 seconds
5:59:03
17:59:03
Will correct for
hours, minutes,
and seconds.
57 seconds on,
63 seconds off
11 times from
5:59:03 to
6:20:00
58 minute correction
Honeywell ST402, 403, 404, 410, 411,
412, 413, 802, 803, 804, 810, 811, 812
& 813
Faraday 1310, 1311, 1320, & 1321
Cincinnati D8
Standard/Faraday 2310 & 2331
007 xx:58:05
Will correct
the minutes
and seconds.
55 seconds
5:05:00
17:05:00 65 seconds on,
25 seconds off
12 times from
5:05:00 to
5:22:35