PM130 PLUS Quickstart
9
Basic Menu
Code Parameter Options Description
ConF
Wiring mode 3OP2 3-wire open delta using 2 CTs
4Ln3 4-wire Wye using 3 PTs (default)
3dir2 3-wire direct connection using 2 CTs
4LL3 4-wire Wye using 3 PTs
3OP3 3-wire open delta using 3 CTs
3Ln3 4-wire Wye using 2 PTs
3LL3 4-wire Wye using 2 PTs
3bLn3 3-wire Broken delta using 2 PTs, 3 CTs
3bLL3 3-wire Broken delta using 2 PTs, 3 CTs
Pt
PT ratio 1.0∗- 6,500.0 The potential transformer ratio
Ct
CT primary current 1-50,000A (5*) The primary rating of the current transformer
d.P PM130E PLUS,
PM130EH PLUS
Power demand period 1, 2, 5, 10, 15*, 20,
30, 60, E The length of the period for power demand calculations, in
minutes. E = external synchronization
n.dp PM130E PLUS
PM130EH PLUS
Number of power
demand periods 1-15
(1*)
The number of demand periods to be averaged for sliding window
demands
1 = block interval demand calculation
A.dP
Ampere/Volt demand
period 0-1800
(900*) The length of the period for volt/ampere demand calculations, in
seconds. 0 = measuring peak current
Freq
Nominal frequency 25, 50, 60, 400 (Hz)
The nominal power utility frequency
•- Default setup
Communication Port Menu
COM1 setting
Code Parameter Options Description
Prot
Communications protocol ASCII∗, rtu, dnP3 ASCII, Modbus RTU (default) or DNP3.0 protocol
rS
Interface standard 485 RS-485 interface (default)
Addr
Address ASCII:
0
(default)
- 99
, Modbus:
1
(default)
-247
, DNP3.0:
0
(default)
-255
bAud
Baud rate 110, 300, 600, 1200, 2400, 4800, 9600 (default), up to 115,200 bps
dAtA Data format 7E, 8E (7/8 bits, even parity), 8n (default) (8 bits, no parity)
COM2 setting (optional communication module)
Code Parameter Options Description
Prot
Communications protocol rtu, dnP3, PrFB Modbus/TCP or DNP3/TCP or Profibus DP protocol
rS
Interface standard Eth., PrFB Ethernet interface (default) or Profibus DP
Addr
Address Modbus:
1
(default)
-247
, DNP3.0:
0-65532
, Profibus DP:
0-126