
3.2.3 Mains Voltage Test
The mains AC voltage will be displayed automatically on the main LCD screen.
Check that the voltage is within the correct range 207 - 253 VAC.
The indicated voltage can be toggled between L-N (default), L-E and N-E by
using the voltage button.
Note: All tests are inhibited until the mains voltage appears in the display.
3.2.4 No Trip Loop Testing
This is the default setting for the DL420. This mode is most useful for testing either
at socket outlets, luminaires, or wiring terminals in installations where the circuit
under test is protected by an RCD.
No trip mode testing can be used with the IECP UKA lead when testing at 13A
sockets, or the ITLS 400 at all other points in the circuit. When using the ITLS test
leads the three coloured prods / clips should be connected to the
corresponding live, neutral and earth terminals.
A brief press of the test button will initiate the loop test, after a few seconds the
result will be displayed.
The no trip loop testing mode is a low current measurement technique and is
ideal for use on end circuits. However, low current measurements are more
susceptible to being effected by external factors such as contact resistance or
circuit noise. For this reason we recommend that multiple measurements are
taken and any isolated erroneous results are disregarded. The tester or the
supply should be powered off between consecutive tests.
For safety reasons no trip mode is recommended for all measurements on TT
systems.
3.2.5 No Trip PFC
Once the no trip loop test is complete pressing this button will calculate the
Prospective Fault Current (PFC) . The tester does this by dividing the L - N
voltage by the measured loop impedance.
3.2.6 High Current True Loop Impedance Testing
This is selected by pressing the Ze/DB button and can only be used with the ITLS
400 test leads in two lead mode. This is done by removing the prod of the blue
fuse holder and plugging the exposed 4mm connector into the back of the
green 4mm plug as shown below. Earth and neutral will now be connected and
ready to connect onto the earth conductor to be tested.