Basic documentation
9 TXV 174 05
1.3 ELECTRICAL PARAMETERS
Number of outputs
16
Number of outputs in a group 16 (in 4 groups)
Galvanic isolation from internal circuits yes, groups as well as one another
Diagnostics yes, signalization of closed output
on the module panel
Common pole yes
Output type solid state relay, switching at zero,
unprotected output
Contact type switch-on contacts
Switching voltage Max. 250 V DC
Min. 20 V DC
Switching current Max. 0.25 A
Min. 5 mA
Short-time output overload Max. 1 A
Common pole current Max. 4 A
Switch on period of output Typ. 10 ms
Switch off period of output Typ. 10 ms
Limit values for switching load:
- for resistance load Min. 0.25 A at 230 V AC
- for inductive load AC15 Max. 0.25 A at 230 V AC
Switching rate without load Max. 400 switchings / s
Switching rate with nominal load Max. 100 switchings / s
Inductive load treatment external
RC element, varistor
Insulation voltage between inputs and internal circuits 3750 V AC
Insulation voltage between groups of inputs 1000 V AC
Module power loss Max. 5 W
Taken input of module from system source Max. 1,8 W
2. PACKAGING, TRANSPORTATION, STORAGE
The module is packed according to internal packing instructions into a cardboard box. This
documentation is enclosed in the packaging. The external packaging is done according to the
quantity and way of transportation into a shipping container being labelled and containing all the
necessary data for transportation.
The goods is transported from the manufacture's facilities as agreed when placing an order.
Transportation of the goods by the customer must be pursued by covered transport means and
in the position as indicated on the packaging. The shipping containers must be fixed in such a
way to avoid accidental spontaneous movement and damage of the external container during
transport.
During transportation and storage, the product must be protected from direct influence of
atmospheric actions. Transportation of the product is permited within a temperature range of
-25 °C to 70 °C, relative humidity of 10 % to 95 % (without condensation) and minimum
atmospheric pressure higher than 70 kPa.
The product must be stored only in clean spaces free from conductive dust, aggressive
gases and vapours. The optimum storage temperature is 20 °C.