Vent-Axia Sentinel Manuale del proprietario

Copyright © 2009 Vent-Axia Limited. All rights reserved.
Sentinel
Totus 2 D-ERV
Installation, Operation & Maintenance
Stock Ref. N°
TOTUS2MINI
TOTUS2MINI/CP
TOTUS2MIDI
TOTUS2MIDI/CP
TOTUS2MAXI
TOTUS2MAXI/CP
PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

Safety Information
2
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
IMPORTANT
PLEASE READ THESE INSTRUCTIONS
CAREFULLY BEFORE COMMENCING
INSTALLATION AND LEAVE THEM WITH
THE END USER.
1. THESE UNITS MUST BE SITED AND CONNECTED IN
ACCORDANCE WITH CURRENT IEE REGULATIONS, BS7671
(UK) OR THE APPROPRIATE STANDARDS IN YOUR
COUNTRY.
2. INSTALLATION SHOULD BE BY A QUALIFIED ELECTRICIAN
AND INSTALLER.
3. ALL REGULATIONS AND REQUIREMENTS MUST BE
STRICTLY FOLLOWED TO PREVENT HAZARDS TO LIFE AND
PROPERTY, BOTH DURING AND AFTER INSTALLATION, AND
DURING ANY SUBSEQUENT SERVICING AND MAINTENANCE.
4. THESE UNITS MUST BE EARTHED.
5. SITE THE UNIT AWAY FROM DIRECT SOURCES OF HEAT.
AMBIENT TEMPERATURE RANGE 10 TO 40ºC.
6. WHEN INSTALLING UNIT, TAKE CARE NOT TO DAMAGE
ELECTRICAL OR OTHER HIDDEN UTILITIES.
7. CHECK THE DETAILS ON THE RATING LABEL FOR
CORRECT VOLTAGE AND ELECTRICAL RATING.
8. THE INSTALLER IS RESPONSIBLE FOR THE INSTALLATION
AND ELECTRICAL CONNECTION OF THE SENTINEL SYSTEM
ON SITE. IT IS THE RESPONSIBILITY OF THE INSTALLER TO
ENSURE THAT THE EQUIPMENT IS SAFELY AND SECURELY
INSTALLED AND LEFT ONLY WHEN MECHANICALLY AND
ELECTRICALLY SAFE.
9. DUE TO THE WEIGHT OF THE UNITS, IT IS
RECOMMENDED THAT MULTIPLE PERSONS ARE INVOLVED
IN THE INSTALLATION. AT ALL TIMES, INSTALLATION
PRACTICES MUST COMPLY WITH RELEVANT HEALTH AND
SAFETY LEGISLATION.
10. SENTINEL AIR HANDLING UNITS ARE DESIGNED AND
SPECIFIED FOR USE WITH VENT-AXIA CONTROLS,
DAMPERS, GRILLES AND ACCESSORIES.
11. THIS APPLIANCE IS NOT INTENDED FOR USE BY YOUNG
CHILDREN OR INFIRM PERSONS WITHOUT SUPERVISION.
12. YOUNG CHILDREN SHOULD BE SUPERVISED TO ENSURE
THAT THEY DO NOT PLAY WITH THE APPLIANCE.
13. PRECAUTIONS MUST BE TAKEN TO AVOID THE
BACKFLOW OF GASES INTO THE ROOM, FROM THE OPEN
FLUE OF GAS OR OTHER FUEL BURNING APPLIANCES.
14. THIS UNIT SHOULD NOT BE USED IN A GREASE-LADEN
ATMOSPHERE. IF THE UNIT IS TO BE USED IN A GREASE-
LADEN ATMOSPHERE SUITABLE DUCT FILTRATION SHOULD
BE USED.
PRODUCTS COVERED
Thank you for purchasing Sentinel Totus 2 D-ERV.
This document describes the installation and
commissioning of your equipment to help get your
equipment up and running. It also provides essential
maintenance and troubleshooting information to assist the
operation and prolong the lifetime of your equipment.
This document covers the Sentinel Totus 2 D-ERV series
detailed in the following table.
Table 1: Products Covered by this Document
Model Number Description
TOTUS2MINI Totus 2 Mini
TOTUS2MINI/CP Totus 2 Mini/ Constant Pressure
TOTUS2MIDI Totus 2 Midi
TOTUS2MIDI/CP Totus 2 Midi/Constant Pressure
TOTUS2MAXI Totus 2 Maxi
TOTUS2MAXI/CP Totus 2 Maxi/Constant Pressure
See Technical Specification for details of these models.

About this Document
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
3
CONTENTS
Product Description 4
Sentinel Totus 2 D-ERV............................................................... 4
Technical Specification 6
Sentinel Totus 2 D-ERV Technical Specification.......................... 6
Commissioning Record................................................................ 6
Dimensions.................................................................................. 7
Installation 11
Installing Your Energy Recovery Ventilation System...................11
Before Installing Your Equipment................................................12
Physical Installation ....................................................................13
Electrical Installation...................................................................17
Switching On/Off.........................................................................23
Commissioning 24
Commissioning Your Energy Recovery Ventilation System.........24
Commissioning Screens .............................................................26
The Settings Code......................................................................37
Writing Down the Settings Code .................................................38
Default Settings ..........................................................................39
Restoring Settings 40
Restore Settings Screens ...........................................................40
Operation and Monitoring 42
About Operation and Monitoring .................................................42
Status Monitoring Screens..........................................................42
Maintenance 46
Caring for Your Unit....................................................................46
3-Monthly Maintenance ..............................................................46
12-Monthly Maintenance ............................................................46
5-Yearly Maintenance.................................................................46
Removal/Replacement of Parts 47
Cover Removal/Replacement .....................................................47
Filter Removal/Replacement (Roof-Mounted) .............................49
Filter Removal/Replacement (Ceiling-Mounted)..........................49
Motor Removal/Replacement (Roof-Mounted)............................50
Motor Removal/Replacement (Ceiling-Mounted).........................51
Float Switch Removal/Replacement (Roof-Mounted)..................52
Float Switch Removal/Replacement (Ceiling-Mounted) ..............53
Condensate Pump Removal/Replacement (Roof-Mounted)........54
Condensate Pump Removal/Replacement (Ceiling-Mounted) ....55
Filter Removal/Replacement (Maxi)……………..………………....56
List of Spares .............................................................................57
Troubleshooting 58
Diagnosing a Problem ................................................................58
Diagnostic Codes .......................................................................58
Fault LED/Status Relay ..............................................................59
Power Supply Troubleshooting ...................................................59
Airflow/Temperature Troubleshooting .........................................60
Condensate Troubleshooting......................................................61
Appendix A: Glossary 62
Terms and Abbreviations ........................................................... 62
Appendix B: Options and Accessories 63
Sentinel Totus............................................................................ 63
Appendix C: Main Controller PCB Terminals 64
Terminals................................................................................... 64

Product Description
4
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
Product Description
Sentinel Totus 2 D-ERV
Sentinel Totus 2 Demand Energy Recovery Ventilation (D-ERV) is a heat recovery demand ventilation
system designed to meet modern building management and control principles.
Employing a range of sensors to manage the system, demand is typically sensed by PIR, temperature,
humidity, air quality, carbon dioxide sensors or other types of Vent-Axia proprietary sensors (see Appendix B:
Options and Accessories on page 63 for details).
It can respond to the ventilation requirements of a room by providing airflow only when it is required and at the
level that is required, using only the energy that is needed, while recovering maximum energy from the
extracted air and transferring it to the fresh supply air. This overcomes many of the drawbacks encountered with
traditional fixed volume ventilation systems, which operate irrespective of the occupancy of the room, leading to
over ventilation and a wasteful use of energy.
Note that the unit contains heaters, which automatically prevent the heat recovery cell from freezing and can
also be used to “Top Up” the air temperature to the room.
Models
Mini designed to operate at airflows of up to 650 m
3
/hr at 150 Pa.
Midi designed to operate at airflows of up to 1000 m
3
/hr at 150 Pa.
Maxi designed to operate at airflows of up to 2000 m
3
/hr at 150 Pa
Figure 1: Sentinel Totus Mini & Midi 2 D-ERV
External
Ambient Air
I
nternal
Room Air
Commissioning
Interface
Main Controller
PCB Access Panel Condensate
Drain
Heaters
Counter-flow Cell Summer Bypass
DC Motors
T4
T1
T1-T4 = internal
temperature
sensors
Filter Water Pump
CP Switch
(Optional)
Filter
T
3
T
2

Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
5
Figure 2: Sentinel Totus 2 Maxi D-ERV
T
3
T
2
T1
T4
Counter-flow Cell
Heaters
DC Motor
Filter
Summer Bypass
Entry Panel
Main
Controller
PCB Access
Panel
Access
Panel
I
nternal
Room Air
External
Ambient Air
T1-T4 = internal
temperature
sensors

Technical Specification
6
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
Technical Specification
Sentinel Totus 2 D-ERV Technical Specification
Performance Mini Midi Maxi
Airflow (nominal) 650 m
3
/hr at 150 Pa 1000 m
3
/hr at 150 Pa 2000 m
3
/hr at 150 Pa
Power
AC Voltage Input 220-240 V ac (single phase)
AC Frequency Input 50/60 Hz nominal
Supply Fuse or Cct Breaker 16 A 16 A 32A
Rated Current 12 A 12 A 20A
Rated Power 1825 W 2500 W 5000W
Total Fan Power (max.) 325 W 500 W 1000W
Total Frost Heater (max.) 1.5 kW 2 kW 4kW
Power (standby) 0.6 W 0.6 W 0.6 W
DC Voltage Output 24 V dc (18-30 V dc) at 350 mA (max.) for switches and sensors
Battery See Table 6: 5 12-Monthly Maintenance on page 46
Product Fuses
Power PCB See Table 11: Internal Fuse Values and Types on page 60
Main Controller PCB See Table 11: Internal Fuse Values and Types on page 60
Physical
Height/Width/Depth Mini, Midi & Maxi see page 7 and 8
Weight 145 kg 167 kg 250 kg
Environmental
IP Rating - Unit IPX4
IP Rating - Commissioning
Interface
IP42
Operating Temperature -10°C to +40°C
Operating Humidity 0% to 95% (non-condensing) – weatherproof unit option
Storage Temperature -10°C to +40°C
Storage Humidity 0% to 95% (non-condensing)
Condensate Pump 12 m max head, 25 m max horizontal distance, but 150 max head X distance
Software Version V25
For all other technical details, please see the Product Catalogue or our website at www.vent-axia.com.
Commissioning Record
Record the unit commissioning settings here.
Date Settings Code Who
For details of the settings code, see
The Settings Code on page 37.

Technical Specification
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
7
Dimensions
Model
Dimensions (mm)
a b c d e f g h i j k l m n o p q r
Mini 1800 1920 352 940 900 450 250 - 60 142 174 962 153 42 188 375 72 1656
Midi 1900 2020 350 1290 1250 538 400 250 60 220 175 1315 147 47 332 526 72 1758
Maxi 1800 1925 660 1212 1130 530 400 - 60 710 578 - - - - 635 - -
Mini
Midi

Technical Specification
8
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
Maxi
Figure 3: Unit Dimensions for Mini, Midi & Maxi

Technical Specification
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
9
Filter and Control Box Access

Technical Specification
10
Sentinel Totus 2 D-ERV Installation, Operation and Maintenance
MAXI