Operating instructions
Control unit - CGL
20.0 °C
Friday
31/10/08
12 : 16
Zone 1

3063527_2013082
Table of contents
Safety instructions, service / repair.............................................................................. 4
Standards and regulations ........................................................................................... 5
Unit description / disposaland recycling ..................................................................... 6
Zoning.............................................................................................................................. 7
Installation as an external remote control ................................................................... 8
Electrical connection ..................................................................................................... 8
BML overview ................................................................................................................. 9
Control level 1.......................................................................................................... 10-13
L.h. rotary selector, program selection....................................................................... 10
R.h. rotary selector..................................................................................................... 10
Program selection ................................................................................................. 10-11
Automatic mode ................................................................................................... 10
Manual mode.........................................................................................................11
Ventilation mode....................................................................................................11
Standby mode .......................................................................................................11
Info key ................................................................................................................. 11-12
Temperature selection key ......................................................................................... 12
Speed adjustment key ............................................................................................... 12
Display explained ......................................................................................................... 13
Control level 2.......................................................................................................... 14-24
Main menu overview .................................................................................................. 14
Displays ..................................................................................................................... 15
Acknowledge faults .................................................................................................... 15
Basic settings............................................................................................................. 16
Language ............................................................................................................. 17
Date...................................................................................................................... 17
Time ..................................................................................................................... 17
Automatic summertime......................................................................................... 18
Key lock................................................................................................................ 18
Zone Z1................................................................................................................ 19
Day temperature................................................................................................... 19
Economy temperature for heating........................................................................ 19
Backup temperature for heating........................................................................... 19
Speed adjustment ................................................................................................ 20
Setback mode program........................................................................................ 20
Supply air minimum limit ...................................................................................... 20
Enable night ventilation ........................................................................................ 21
Time program............................................................................................................. 21
Switching times, factory setting............................................................................ 22
Holiday program......................................................................................................... 23
Specialist.................................................................................................................... 24

3063527_201308 3
Control level 3.......................................................................................................... 24-32
Code scan.................................................................................................................. 24
New conguration / Sensor check ............................................................................. 24
Zone designat ............................................................................................................ 24
Ventilation unit parameters ........................................................................................ 25
Relay test ................................................................................................................... 25
Zone reset.................................................................................................................. 25
Setting parameters....................................................................................................... 26
Specialist parameter list - overview ...................................................................... 26-27
Parameters / function description ......................................................................... 28-32
Master reset / standard functions.......................................................................... 33-34
Motor protection ......................................................................................................... 33
Room frost protection................................................................................................. 33
Central heating backup mode .................................................................................... 34
Supply air minimum limit for heating .......................................................................... 34
Filter contamination fault trigger................................................................................. 34
Active lter monitor .................................................................................................... 34
Fan run-on time.......................................................................................................... 34
External ON/OFF ....................................................................................................... 34
Additional functions................................................................................................ 34-36
Room/supply air cascade control............................................................................... 35
Night ventilation ......................................................................................................... 35
Preheater coil, HR ice guard...................................................................................... 36
Condensate overow ................................................................................................. 36
Summer shutdown ..................................................................................................... 36
Heat recovery............................................................................................................. 36
HR ice guard .............................................................................................................. 36
Fire alarm................................................................................................................... 36
CO2 control..................................................................................................... 31, 32, 37
Sensor resistances....................................................................................................... 37
Specication ................................................................................................................. 38
System conguration................................................................................................... 39
Terminal assignments.................................................................................................. 40
Fault messages........................................................................................................ 41-43
Wiring diagram ........................................................................................................ 44-47
Menu structure......................................................................................................... 48-51
Table of contents

3063527_2013084
Safety instructions
The following symbols are used in this instruction manual. This
important information concerns personal as well as operational
safety.
"Safety instructions" must be complied with to the letter, to prevent
risks and injuries to individuals and material losses on the appliance.
Danger through 'live' electrical components!
Please note: Turn off the ON/OFF switch before removing the
casing.
Never touch electrical components or contacts when the ON/OFF
switch is in the ON position. This would lead to a risk of electrocution
that may lead to injury or death.
"Note" indicates technical instructions that must be observed to
prevent material losses and equipment malfunctions.
Even when the unit has been shut down, voltage will still be present
at terminals and connections of the EC fans. This means there is
a risk of electric shock that could result in injury or death.
Never touch the EC fans until ve minutes after disconnecting the
power across all poles have elapsed.
Please note
Safety instructions
Service / Repair - Regularly check the perfect function of all electrical equipment.
- Only qualied personnel may remove faults or repair damage.
- Only replace faulty components or equipment with original Wolf
spare parts.
- Observe specied electrical fuse ratings (see specication).
Any damage or loss resulting from technical modications to Wolf
control units is excluded from our warranty.
Please note
Service / Repair

3063527_201308 5
Standards / Regulations
- According to DIN EN 50110-1, only qualied electricians may
carry out the installation and commissioning of the ventilation
control unit and connected accessories.
- Observe all regulations stipulated by your local power supply
utility and all VDE or local regulations.
- DIN VDE 0100 regulations regarding the installation of high
voltage systems up to 1000 V
- DIN VDE 0105-100 Operation of electrical plants
- Use exclusively original Wolf accessories (electric heater coil,
condensate pump, servomotors, etc.), otherwise the Wolf
warranty will be void.
Only use cables that meet local wiring regulations with regard to
voltage, current, insulation material, load etc. Always t an earth
conductor.
Power supply:
An externally accessible, omnipolar isolator must be installed
with the appliance. Power cable, external: 3 x 2.5 mm².
Fuse/MCB protection: 230 V/16 A.
RCD
Only AC/DC-sensitive RCDs of type B with 300 mA rating are
permissible.
Connect the power cable and accessories in accordance with
the wiring diagram provided.
A high leakage current can be expected due to the EC
motors. Ensure that a secure earth connection is in place
before connecting the power supply and commencing
commissioning.
For Austria, the ÖVE regulations and local building regulations
apply.
Installation /
Commissioning
Warnings - Removing, bypassing or disabling of safety and monitoring
equipment is not permissible.
- The system must only be operated if it is in perfect technical
condition. Immediately have any faults and damage that may
impact on safety removed.
The appliance and control unit accessories comply with the
following regulations:
EC Directives
- 2006/95/EC Low Voltage Directive
- 2004/108/EC EMC Directive
EN Standards
- EN 60730-1 Automatic electrical controls for household and
similar use
- EN 60730-2-11 Particular requirements for temperature
sensing controls
- EN 61000-6-2 EMC Immunity for industrial environments
- EN 61000-6-3 EMC Emission standard for residential
environments
Standards / Directives

3063527_2013086
The control panel is designed for regulating large area ventilation
units with variable speed EC motors.
Other functions
- HR control 0 - 10 V
- CO2-based fan speed matching
- Electric reheater coil: variable control 0 - 10 V
- Room / supply air cascade control or supply air control
- Night ventilation
- Electric preheater coil:
Switching ON/OFF by outside temperature
The control unit can be operated with the programming module
for ventilation units (BML programming module, material number
2744634). The BML programming module can also be used to
program switching times, to modify parameters and to display
fault messages.
The control unit has an eBUS interface and can therefore be fully
integrated into the Wolf control system.
There can only be one BML in any one system (eBUS).
Up to 7 CGL units can be operated with one programming unit.
Please note
Unit description
Unit description
Observe the following information regarding the disposal of faulty
system components or the system at the end of its service life:
Dispose of all components in accordance with applicable
regulations, i.e. separate material groups correctly. The aim should
be the maximum possible amount of basic materials recycled and
the lowest possible environmental impact.
Never dispose of electrical or electronic scrap through household
waste, but recycle it appropriately.
Generally, dispose of materials in the most environmentally
responsible manner according to environmental, recycling and
disposal standards.
Disposal and recycling
The ventilation unit is designed for air intake temperatures between
-20 °C and +40 °C. Only store the ventilation unit in dry conditions
at an ambient temperature between -25 °C and +55 °C.
Wolf CGL ventilation units are designed to heat and lter normal
air. The use of these units in wet rooms or rooms with explosive
atmospheres is not permissible. Handling very dusty or aggressive
media is not permissible.
Any on-site modication or unintended use of the unit is not
permissible and Wolf GmbH accepts no liability for any damage
caused as a result.
Intended use

3063527_201308 7
Zoning
Zoning When more than one CGL is controlled with one programming unit,
the zone for each appliance must be set using the DIP switches
on the control PCB (in the control panel).
If only one zone is to be connected, the following chapter can
be skipped.
Multiple zones in one
system
The three switches on the left hand side of the 4-position DIP switch
can be used to assign the ventilation unit to a zone.
Up to seven zones are possible in one system.
Zone setting
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Fig.:
DIP switches on the
control PCB
DIP switches
Control PCB
X1
Never pull out the coding card X1, otherwise malfunctions may
result.
Please note

3063527_2013088
Installation as an external remote
control
Wall mounting base
installation
- Remove the wall mounting base from its packaging.
- Secure the wall mounting base on a ush-mounting box
(Ø 55 mm) or directly on the wall.
Wall mounting base
Fixing holes Fixing holes
Installation of BML on wall mounting base
Wall mounting base
Mat. no. 2744275
60
100
Electrical connection of
remote control
- The electrical connection must be carried out only by a qualied
electrician.
- Never route sensor leads alongside mains power cables.
- Use the repair switch to switch off the power supply
- Wire the wall mounting base with a four-core cable (minimum
cross-section 0.5 mm²) in accordance with the diagram
eBUS Terminal strip
Wall mounting base
+ -
+ -
Recommended cables
and
minimum cable
cross-sections:
H05VV-F 3 x 2.5 mm² power cable (230 V)
H05VV-F 4 x 1.0 mm² Open/Close servomotor 230 V
H05VV-F 2 x 0.5 mm² BUS cable (<400 m length)
Fuse/MCB protection: Power supply 230 V 1 x 16 A
ϑ
Outside temperature sensor

3063527_201308 9
BML overview
L.h. rotary selector R.h. rotary selector
Info key
Temperature
adjustment
Speed adjustment
DisplayStatus indicator
Minimum fresh air proportion
(no function)
20.0 °C
Friday
31/10/08
12 : 16
Zone 1
Room temperature / extract air temperature
Time alternating with
outside temperature

3063527_20130810
Program selection You can select the programs listed below by turning the l.h. rotary
selector.
The arrow on the l.h. edge of the display points to the selected
program.
R.h. rotary selector
The right hand rotary selector is used for all programming steps.
Turning the rotary selector enables you to select the required
menu item.
Pressing the r.h. rotary selector conrms the programming step.
L.h. rotary selector, program selection
This rotary selector enables the program to be selected. The rotary
selector can be rotated indenitely, without an end stop. You will
feel it click into each position as it rotates. The selected function
is indicated by an arrow in the display.
Control level 1
Automatic mode
Ventilation according to a time switch program. Call-up of HR,
reheater and fan according to demand.
As shown in the diagram, you can preselect the operating mode
via the time program when the system has been switched off.
06:00 22:00
On
Off
„Day mode”
Time
Setback mode program
Selection:
- Economy operation
- Backup mode (factory setting)
- Standby
- Summer ventilation
Backup mode Backup mode
07:00 14:00
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali Wolf Unità di controllo

Wolf
Wolf R33/4 DigiComfort (Theta) Guida rapida

Wolf
Wolf BM-Solar Manuale utente

Wolf
Wolf FWS-2-60 Manuale utente

Wolf
Wolf RK-2 Guida rapida

Wolf
Wolf Link home Manuale utente

Wolf
Wolf BMK Manuale utente

Wolf
Wolf SM2 Manuale utente

Wolf
Wolf BML-EXCELLENT Manuale utente

Wolf
Wolf SW MV Manuale utente

Wolf
Wolf 3064055-201508 Manuale utente
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente