Xtreme G90 Manuale utente

G90 Online UPS
1000VA, 2000VA, 3000VA Models
User & Installaon Manual
www.xpcc.com | © 2015 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 2/5/15)

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 2
Uninterrupble Power Supply
Table of Contents
Introducon.................................................................................................7
Product Descripon......................................................................................7
Double Conversion Online Technology............................................................................................7
Diagnosc Tests...............................................................................................................................8
System Conguraon...................................................................................8
Communicaon Connecons.........................................................................................................10
Emergency Power O (EPO) Port...................................................................................................11
Hardware Installaon Guide.......................................................................12
Safety Informaon.........................................................................................................................12
Storage and Transportaon...........................................................................................................12
Environment...............................................................................................13
UPS Installaon..........................................................................................13
Connecng the UPS Internal Baeries...........................................................................................13
Connecng Extended Baery Packs (EBPs)...................................................................................15
Rack-mount Installaon.................................................................................................................17
Tower Installaon..........................................................................................................................19
UPS Input Connecon....................................................................................................................21
UPS Output Connecon.................................................................................................................21
Starng the UPS............................................................................................................................ 21
Operaons.................................................................................................23
Front Panel Control Funcons.......................................................................................................23
Indicator Descripons....................................................................................................................23
Buon Descripons.......................................................................................................................24
Working Status of Indicators..........................................................................................................24
Display Funcons...........................................................................................................................25
Parameters Inquiring.....................................................................................................................27
User Sengs..................................................................................................................................29
Operang Mode Descripon.......................................................................33

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 3
Uninterrupble Power Supply
Startup Operaon..........................................................................................................................34
Shutdown Operaon......................................................................................................................34
UPS Self-Test/Mute Test Operaon................................................................................................35
Conguring Baery Sengs..........................................................................................................35
Using UPS with Generator...........................................................................35
Communicaon..........................................................................................36
Installing Communicaon Opons and Control Terminals............................................................36
Troubleshoong.........................................................................................39
Fault Codes....................................................................................................................................40
UPS Maintenance..........................................................................................................................40
UPS and Baery Care.................................................................................................................... 40
Storing the UPS and Baeries........................................................................................................41
Maintenance..................................................................................................................................41
Replacing Baeries (QUALIFIED SERVICE PERSONNEL ONLY)........................................................41
Replacing Baery Trays in UPS and EBPs.......................................................................................42
Specicaons.............................................................................................45
Shipping List.............................................................................................. 46
Obtaining Service.......................................................................................47
Xtreme Power Conversion Limited Warranty...............................................48
Appendix A: G90-EBP1, G90-EBP2 User Guide.............................................49
Introducon...................................................................................................................................49
Installaon.....................................................................................................................................49
Operaon.......................................................................................................................................51
Maintenance..................................................................................................................................51
Tesng New Baeries....................................................................................................................53
Recycling the Used Baery............................................................................................................53
Specicaons.................................................................................................................................54

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 4
Uninterrupble Power Supply
Thank you for selecng this uninterrupble power supply (UPS). It provides you with protecon for connected
equipment. Please read this manual before installing the G90 Series UPS models G90-1000, G90-2000, or G90-
3000 as it provides important informaon that should be followed during installaon and maintenance of the UPS
and baeries, allowing you to correctly set up your system for the maximum safety and performance. Included is
informaon on customer support and service, if it is required. If you experience a problem with the UPS, please
refer to the Troubleshoong secon in this manual to correct the problem. If the problem is not corrected, please
collect informaon so that the Technical Support personnel can more eecvely assist you.

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 5
Uninterrupble Power Supply
Important Safety Instrucons: (Save These Instrucons)
CAUTION! (UPS having Internal Baeries): Risk of electrical shock – Hazardous live parts inside this unit are ener-
gized from the baery supply even when the input AC power is disconnected.
CAUTION! (No User serviceable Parts): Risk of electrical shock, do not remove cover. No user serviceable parts
inside. Refer servicing to qualied service personnel.
CAUTION! (Non-isolated Baery supply): Risk of electric shock, baery circuit is not isolated from AC input, haz-
ardous voltage may exist between baery terminals and ground. Test before touching.
WARNING! (Fuses): To reduce the risk of re, replace only with the same type and size of fuse.
WARNING! Unit intended for installaon in a controlled environment.
CAUTION! Do not dispose of baeries in a re, the baery may explode.
CAUTION! Do not open or mulate the baery, released electrolyte is harmful to the skin and eyes.
CAUTION! A baery can present a risk of electric shock and high short circuit current. The following precauon
should be observed when working on baeries:
• Remove watches, rings or other metal objects.
• Use tools with insulated handles.
To reduce the risk of electric shock, disconnect the UPS from the main supply before installing a computer inter-
face signal cable. Reconnect the power cord only aer signaling interconnecons have been made.
Servicing of baeries should be performed or supervised by personnel with knowledge of baeries and the re-
quired precauons. Keep unauthorized personnel away from baeries.
These UPS units are extremely heavy. Cauon should be taken in moving and posioning equipment.
The instrucons contained within this safety manual are deemed important and should be closely followed at all
mes during installaon and follow-up maintenance of the UPS and baeries.

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 6
Uninterrupble Power Supply
CAUTION
The unit has a dangerous amount of voltage. If the UPS indicator is on, the unit’s outlets may have a dan-
gerous amount of voltage even when not plugged into the wall outlet because the baery may connue
to supply power.
Care should be taken to undertake installaon indoors, free from electrically-conducve parcles which
are under temperature and humidity control, in order to reduce the risk of electric shock.
It is best to disconnect the device using the power supply cord. Ensure that the equipment is placed in a
posion near the outlet where easily accessible.
Except for replacing the baeries, all servicing on this equipment must be carried out by qualied service
personnel.
Before conducng any maintenance, repair, or shipment, rst ensure that everything is turned o com-
pletely and disconnected.
For addional safety instrucons, please use the Safety Manual as a reference.
Special Symbols
The following symbols used on the UPS warn you of precauons:
RISK OF ELECTRIC SHOCK - Please observe the warning that a risk of electric shock is present
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to the operator’s manual for addional informaon,
such as important operang and maintenance instrucons.
SAFE GROUNDING TERMINAL - Indicates primary safe ground
LOAD ON/OFF – Pressing the buon turns on/o the output receptacles and the indicator light.
RJ45 RECEPTACLE – The receptacle provides network interface connecons and telephone or telecommu-
nicaons equipment should not be plugged into it.
Please do not discard of the UPS or the UPS baeries as the UPS may have valve-regulated lead-acid bat-
teries. Please recycle baeries appropriately.

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 7
Uninterrupble Power Supply
Introducon
The informaon provided in this manual covers single phase 1000 – 3000 VA uninterrupble power system, their
basic funcons, operang procedures, opons available and emergency situaons. It also includes informaon on
how to ship, store, handle, and install the equipment. Only detailed requirements of the UPS units are described
herein, and installaon must be carried out in accordance with this manual. Electrical installaon must also care-
fully follow local legislaon and regulaons. Only qualied personnel should conduct these installaons as failure
to acknowledge electrical hazards could prove to be fatal.
Product Descripon
Many dierent kinds of sensive electrical equipment can be protected by an Uninterrupble Power Supply (UPS)
including computers, workstaons, process control systems, telecommunicaons systems, sales terminals, other
crical instrumentaon, etc. The purpose of the UPS is to protect these systems from poor quality ulity power,
complete loss of power, or other associated problems.
Electrical interference exists in many forms, causing problems in AC power, from lightning, power company ac-
cidents and radio transmission motors, air condioners, and vending machines. Protecon of sensive electrical
equipment is vital to protect against power outages, low or high voltage condions, slow voltage uctuaons,
frequency variaons, dierenal and common-mode noise, transients, etc.
To prevent power line problems from reaching crical systems causing damage to soware, hardware, and equip-
ment malfuncons, the UPS maintains constant voltage, isolang crical load output and cleaning the ulity AC
power.
Double Conversion Online Technology
A double conversion on-line technology UPS provides completely isolated, clean, uninterrupted single-phase pow-
er to your crical systems, while maintaining the baeries for their maximum potenal. In the event that the
power failure lasts longer than the UPS backup me, the UPS will shut down avoiding baery damage. When the
input AC voltage returns, the UPS will automacally return online to recharge the baeries.
As shown in block diagram:
• An input lter reduces transients on the incoming ulity.
• To maintain full baery charge, the AC input power is reced and regulated in the recer feeding power
to the baery converter and inverter.
• DC power is converted to AC in the inverter, passing it on to the load.
• Power is maintained from the baery during a power failure.
• The converter increases voltage appropriately for the inverter.

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 8
Uninterrupble Power Supply
Block Diagram
Diagnosc Tests
When the UPS is started, a diagnosc test is automacally executed, checking the electronics and baeries, report-
ing any problems on the LCD display.
System Conguraon
The UPS device and the internal baeries make up the system. Depending on the site and load requirements of the
installaon, certain addional opons are available for the soluon.
Planning a UPS system, the following should be taken into consideraon:
• The total demand of the protected system shall dictate the output power rang (VA). Allow a margin for
future expansion or calculaon inaccuracies from measured power requirements.
• Backup me required will indicate the baery size needed. If the load is less than the UPS nominal power
rang, then actual backup me is longer.
• The following opons are available:
o Connecvity Opons
SNMP/WEB card
Dry contact card
o Extended Baery Packs
G90-EBP1 for use with the G90-1000
G90-EBP2 for use with the G90-2000 and G90-3000
See the Specicaon secon of this manual for addional model informaon.

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 9
Uninterrupble Power Supply
UPS FRONT VIEW
EBP FRONT VIEW
G90-1000 REAR VIEW DIAGRAM
G90-2000 REAR VIEW DIAGRAM
G90-3000 REAR VIEW DIAGRAM

Xtreme Power Conversion Corporaon
G90 User’s Manual
Page 10
Uninterrupble Power Supply
G90-EBP1 BATTERY PACK REAR VIEW DIAGRAM
G90-EBP2 BATTERY PACK REAR VIEW DIAGRAM
FRONT PANEL
Communicaon Connecons
To allow for unaended UPS shutdown/start-up and status monitoring, connect one end of the communicaon
cable to the USB/RS232 port and the other to the communicaons port on your PC or server. With the monitoring
soware installed, the UPS can be scheduled for shutdown/start-up and monitoring of the UPS status through the
PC or server.
Indice
Altri manuali Xtreme UPS
Manuali UPS popolari di altre marche

Pylontech
Pylontech Victron & Pylontech US5000 Manuale utente

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuale utente

Mecer
Mecer ME-1000-WTU Manuale utente

Mustek
Mustek PowerMust 530(B) Plus Manuale di installazione e funzionamento

Emerson
Emerson Liebert NXL series Manuale utente

MAKELSAN
MAKELSAN BOXER SERIES Manuale utente