Xtreme P90L Guida

P90L 6kVA & 10kVA Online UPS
6kVA, 10kVA Models
User & Installaon Manual
www.xpcc.com | © 2015 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 5/26/15)

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 2
Uninterrupble Power Supply
Please comply with all warnings and operang instrucons in this manual.
Save this manual and read the following instrucons carefully before install-
ing the unit. Do not operate this unit before reading all safety informaon
and operang instrucons carefully.

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 3
Uninterrupble Power Supply
Table of Contents
Safety Warnings and EMC Instrucons.........................................................5
UPS Warnings..................................................................................................................................5
Maintenance Warnings....................................................................................................................5
Baery Warnings.............................................................................................................................5
Standards.........................................................................................................................................6
Installaon...................................................................................................7
UPS Unpacking and Inspecon........................................................................................................7
Rear Panel View...............................................................................................................................7
System Single Line Diagram...........................................................................................................10
Rack/Tower Installaon.................................................................................................................10
UPS Electrical Installaon..............................................................................................................11
Operaons.................................................................................................13
Operang Mode/Status Descripon..............................................................................................13
Buon Operaon...........................................................................................................................13
LED Indicators................................................................................................................................14
Audible Alarm................................................................................................................................14
UPS Operaon...............................................................................................................................14
LCD Operaon...............................................................................................................................17
Main Interface (Home Screen).......................................................................................................18
Operaon Menu............................................................................................................................18
Control Items.................................................................................................................................19
Measurement Pages......................................................................................................................21
Informaon Pages..........................................................................................................................21
Seng Menu.................................................................................................................................22
Alarm Page....................................................................................................................................25
Troubleshoong.........................................................................................26
Warning Status..............................................................................................................................26
Fault Mode....................................................................................................................................26

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 4
Uninterrupble Power Supply
Trouble Shoong Table..................................................................................................................26
Storage.......................................................................................................29
Specicaons.............................................................................................30
Obtaining Service.......................................................................................31
Xtreme Power Conversion Limited Warranty...............................................32
Xtreme Power Conversion Load Protecon Policy.......................................33
Appendix A: P90L-BP240 User Guide..........................................................36
Important Safety Warnings............................................................................................................36
Installaon and Setup....................................................................................................................36
Storage & Maintenance.................................................................................................................38
Appendix B: P90L-RAIL Installaon Guide...................................................39
Package Contents...........................................................................................................................39
Assembly Steps..............................................................................................................................39
Appendix C: P90L-ISO6MB & P90L-ISO10MB User Guide.............................42
Important Safety Instrucons........................................................................................................42
Rear Panel Explanaon..................................................................................................................43
Installaon And Operaon.............................................................................................................44
Terminal Block Explanaons for Input, Output..............................................................................47
Troubleshoong.............................................................................................................................49
Specicaons.................................................................................................................................49

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 5
Uninterrupble Power Supply
Safety Warnings and EMC Instrucons
This manual contains important instrucons that you should follow during installaon and maintenance of the
UPS and baeries. Please read all instrucons before operang the equipment and save this manual for future
reference.
UPS Warnings
• Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conducve contami-
nants.
• Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and li-
ing the unit.
• Only operate your UPS at indoor temperatures between 32°F and 104°F (between 0°C and 40°C).
• Leave adequate space around all sides of the UPS for proper venlaon.
• Do not install the UPS near magnec storage media, as this may result in data corrupon.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounng in this manner will se-
riously inhibit the unit’s internal cooling, eventually causing product damage not covered under warranty.
• This UPS should be connected with a grounded system. NEC and local electrical codes apply.
• The power supply for this unit must be single-phase rated in accordance with the equipment nameplate.
It also must be suitably grounded
• Use of this equipment in life support applicaons where failure of this equipment can reasonably be ex-
pected to cause the failure of the life support equipment or to signicantly aect its safety or eecveness
is not recommended. Do not use this equipment in the presence of a ammable anesthec mixture with
air, oxygen or nitrous oxide.
• Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
• The UPS is connected to a DC energy source (baery). The output terminals may be live when the UPS is
not connected to an AC supply.
Maintenance Warnings
• Service and repair should be done only by trained personnel. During any service work to the UPS, it should
be turned o or manually bypassed. Note that potenally lethal voltages exist within this unit as long as
the baery supply is connected.
• Your UPS power module and baery module(s) do not require roune maintenance. Do not open them for
any reason. There are no user-serviceable parts inside.
• Even aer the unit is disconnected from the mains, components inside the UPS system are sll connected
to the baery packs which are potenally dangerous.
• Before carrying out any kind of service and/or maintenance, disconnect the baeries and verify that no
current is present and no hazardous voltage exists on PCB components
• Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with
fuses of the same rang and type.
• Verify that no voltage between the baery terminals and the ground is present before maintenance or
repair. In this product, the baery circuit is not isolated from the input voltage. Hazardous voltages may
occur between the baery terminals and the ground.
Baery Warnings
• Do not operate your UPS without connecng it to an external baery module.
• Baeries can present a risk of electrical shock and burn from high short-circuit current. Observe proper

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 6
Uninterrupble Power Supply
precauons.
a) Remove watches, rings, and other metal objects
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of baeries.
e) Disconnect charging source prior to connecng or disconnecng baery terminals.
• Do not dispose of the baeries in a re. Do not open the baeries. The baeries must be disposed of in
accordance with local regulaons.
• Do not short or bridge the baery terminals with any object.
• Unplug and turn o the UPS before performing baery replacement.
• Baery replacement should be performed only by authorized service personnel using the same number
and type of baeries (Sealed Lead-Acid). Use tools with insulated handles. The baeries are recyclable.
• Do not open or mulate the baeries. Released electrolyte is harmful to the skin and eyes, and may be
toxic.
• Do not connect or disconnect baery module(s) while the UPS is operang from the baery supply.
Standards
* Safety
Safety Conformance: IEC/EN 62040-1,UL1778 (4th Edion)
Safety Markings : TUV, cTUVus, CE, UL, cUL, RoHS
* EMI
Conducted Emission...............................:IEC/EN 62040-2 Category C3
Radiated Emission..................................:IEC/EN 62040-2 Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2 Level 4
RS........................................................ ...:IEC/EN 61000-4-3 Level 3
EFT......................................................... :IEC/EN 61000-4-4 Level 4
SURGE................................................... :IEC/EN 61000-4-5 Level 4
CS........................................................... :IEC/EN 61000-4-6 Level 3
Power-frequency Magnec eld.............. :IEC/EN 61000-4-8 Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 7
Uninterrupble Power Supply
Installaon
UPS Unpacking and Inspecon
Open the package and check the contents. The shipping package contains:
• One UPS
• One user manual
• One 3, L6-30R output cord (P90L-6K only)
• One 6, L6-30P input cord (P90L-6K only)
• One monitoring soware CD
• One USB cable
• Two sets of tower stands including feet and extensions
• Two Rack-mounng ears
Note: Before installaon, please inspect the unit. Be sure that nothing inside the package has been damaged dur-
ing transportaon. Do not turn on the unit and nofy the carrier and dealer immediately if there is any damage or
missing parts. Please keep the original packing material in a safe place for future use.
Rear Panel View
P90L-10K Rear Panel
P90L-6K ships with default cord kit
P90L-6K and 10K Input/Output Terminal

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 8
Uninterrupble Power Supply
P90-BP240 Baery Pack Rear Panel
Connecon between P90-BP240 and P90L UPS

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 9
Uninterrupble Power Supply
1. RS-232 communicaon port
2. USB communicaon port
3. EPO (Emergency Power O) connector
4. Share current port (parallel systems only)
5. Parallel port (for future use)
6. Intelligent slot
7. EMBS (External Maintain Bypass Switch) port
8. Cooling fan
9. External baery connector
10. Input circuit breaker
11. Input/output terminal - P90L-6K ships with default cord kit
12. Input terminal
13. Ground
14. Output terminal
15. Baery pack output circuit breaker
Note: EPO connector is normally closed (NC) for normal operaon. To acvate EPO funcon, remove the NC signal.
WARNING: The EPO, RS-232 and USB circuits are IEC 60950 safety extra low voltage (SELV) circuits. This
circuit must be separated from any hazardous voltage circuits by reinforced insulaon.
Normally Closed EPO

Xtreme Power Conversion Corporaon
P90L 6kVA & 10kVA User’s Manual
Page 10
Uninterrupble Power Supply
System Single Line Diagram
System single line diagram is shown below:
Rack/Tower Installaon
Tower Installaon
The UPS system is shipped with four plasc feet and 6 plasc extensions (2 short extensions plus 4 long exten-
sions). These are to be used to install the P90L UPS or UPS and BP240 baery module in tower conguraon:
1. For UPS only, assemble two feet and one short extension together as front support. Assemble rear support
in the same manner.
2. For UPS and Baery Module, assemble two feet and two long extensions together as front support. As-
semble rear support in the same manner.
3. Align the two supports in your installaon area, appropriately 14 inches apart.
4. Then, simply put the UPS module and baery module in the stands as shown in step 3. Be sure that the
UPS LCD display is on the upper half part of front panel.
Step 1 Step 2 Step 3
UPS only
14 in
Questo manuale è adatto per i seguenti modelli
2
Indice
Altri manuali Xtreme UPS
Manuali UPS popolari di altre marche

Pylontech
Pylontech Victron & Pylontech US5000 Manuale utente

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuale utente

Mecer
Mecer ME-1000-WTU Manuale utente

Mustek
Mustek PowerMust 530(B) Plus Manuale di installazione e funzionamento

Emerson
Emerson Liebert NXL series Manuale utente

MAKELSAN
MAKELSAN BOXER SERIES Manuale utente