ADTEK AEM-DRK Manuale utente

AEM-DRK
Multi Circuit Power Meter(DIN rail)
Operation Manual
Rev 1.0
2022-03-25
*41454d44524b-4d-454e-53-41*

II
Content
Chapter 1 Product Overview1
11 Foreword 1
12 Outward & Instructions 1
13 Warning & Criterion 2
Chapter 2 Specifications4
21 Electrical Spec 4
22 Communication Spec 5
23 Operation Interface 5
231 Menu Tree 6
24 Dimensions 8
Chapter 3 Installation10
31 Installation Method 10
311 Environment 10
312 Remind 10
32 Basic Test 11
33 Wiring Instructions 12
331 Wiring Diagram 12
332 Communication Features 14
Chapter 4 Operations15
41 General Operations 15
411 Reading Data 15
4111 Summary Page Inquire 15
4112 Power Parameter Inquire 15
4113 Energy Inquire 16
4114 Alarm Inquire 16
412 Data Clear & Reset 17
413 Meter Information 17
414 User Password 17
415 General Setting 18
4151 Wire System 18
4152 PT Setting 18
4153 CT Setting 19

III
4154 Each Loop Voltage Phase Assign 19
4155 Modify Password 19
4156 Default Page 20
416 Communction 20
4161 Address 20
4162 Baudrate 21
4163 Parity 21
4164 Ethernet Setting 21
4165 Module Control 22
417 Pulse Output 22
4171 Test Pulse 22
4172 Target Loop 22
4173 Energy Type 23
4174 Pre-Divider 23
4175 Time of Level High 23
418 Energy Unit 23
419 Date/Time 24
4191 Backlight Time 24
4192 Date 24
4193 Time 24
4194 Operation Hour Reset 24
4195 Running Hour Reset 25
4110 Demand 25
41101 Mode 25
41102 Period 25
4111 Input/Output 25
41111 Digital Input 25
41112 Relay Output 26
4112 Initial 27
42 Measurement algorithm 27
421 Harmonic 27
422 Demand 28
4221 Sliding Block 28
4222 Fix Block 28
43 Block transfer function 29

IV
44 Data Logging function 29
441 Data logging function setting 29
442 Data log read 32
45 Time of use (TOU) Function 33
451 Season Setting 33
452 TOU Season Format 34
453 Schedule Setting 34
454 Segment Setting 34
455 Tariff Setting 34
456 Holiday Setting 34
457 Holiday schedule 35
458 Weekend Schedule 35
459 Demand 35
4510 TOU Settlement 35
Chapter 5 Troubleshooting36
51 Common Malfunction Analysis 36
511 Power meter dosen't work after power on 36
512 Voltage or current reading in incorrect 36
513 Power or power factor reading is incorrect,but
voltage and current are correct 36
514 RS-485 communication is abnormal 36

1
Chapter 1 Product Overview
1.1 Foreword
Thank you for choosing our product. The instruction manual provides installation and
maintenance for AEM-DRK.
AEM-DRK is a multi circuit power meter designed for power distribution (CAT II-rated
power system) monitoring and control at different types of workplace.
To ensure that it is operated correctly, please read the insturction carefully, and follow
the steps below before operating.
• The work environment should be dry, and it should not contain any corrosive gases
and flammable gases.
• Please follow the wiring diagram to connect wires.
• The grounding project must be implemented, and follow IEC rules in current region.
• Do not remove the meter or change the wiring when it is energized.
• Do not touch the power supply when it is energized to prevent electric shock.
• Please contact your dealer or our customer service center if you have any operating
problem. Also, please contact your dealer or visit our website (http://www.adtek.
com.tw) to download the latest version when the specification is updated.
The AEM-DRK is equipped with LCD showing 5 kinds of measurement data on one
page.
1.2 Outward & Instructions
AEM-DRK

2
1.3 Warning & Criterion
• Attention: installation
• Attention: wiring
• Attention: operation
• Please wear safety equipment when operating the device and
follow the regulations for electrical safety.
• The installation should be operated by licensed engineer who have
read this manual carefully.
• To prevent damage and injuries caused by improper operation,
please operate the device according to the instruction manual.
• The device should be installed in an insulated and fire-resistant
cabinets.
• The secondary side of potential transformer (PT) shouldn't be short-
circuited while using.
• Current transformer (CT) should be open-circuited while using.
• To avoid the cable falling off, and cause damage to the equipment,
please make sure the cable for the secondary side of current
transformer (CT) has been locked out before using.
• Please use current transformer (CT) that meets UL2808 in the
United States/Canada; for other countries, please use current
transformers (CT) that meets IEC61869-2 or required by AHJ.
• Do not work alone.
• Please turn off the power before installation, checking, and
maintenance.
• Please use precision voltage monitoring to ensure that the power
has been turned off.
• Please check all mechanical parts, covers, and doors have returned
to original position before connecting the power, and make sure no
components or tools were left inside the device.

3
• Attention: wiring
• Maintenance and inspection
• Current transformer (CT) must be used with the device when
measuring the current.
• When the measured voltage exceeds the range of rated voltage
for the device( line voltage of 35~690VAC L-L; phase voltage:
20~400VAC L-N), then it must go with a potential transformer (PT).
Please note that the port of the quick coupling is allowed to connect
with one cable only.
• Please re-check the connecting wire and start again if the wire was
pulled out by force.
• Before cleaning the power meter, please turn off the power, and
wipe with dry and soft rag.
• Please do not disassemble the meter while cleaning, or the circuits
will be damaged.
• Do not use the cleaning liquid containing acids or bases.

4
Chapter 2 Specifications
2.1 Electrical Spec.
Accuracy
Power
Voltage 0.2 %
Energy
Active energy 0.5 %
Current 0.2 % Reactive energy 0.5 %
Active power 0.5 % Apparent energy 0.5 %
Reactive power, apparent power 0.5 % Total harmonics in current 1.0 %
Power Factor 0.5 % Total harmonics in voltage 1.0 %
Active power demand 0.5 % Frequency accuracy 0.1 %
Apparent power demand 0.5 % Reactive power demand 0.5 %
Input
Wiring
Single-phase two-wire, 1 CT Three-phase three-wire,
Δ Delta-connection, 2 CT, 2 PT
Single-phase three-wire, 2 CT Three-phase three-wire,
Δ Delta-connection, 1 CT, 2 PT
Three-phase three-wire,
Δ Delta-connection, 3 CT, No PT
Three-phase four-wire,
Y-connection, 3 CT, 3 PT
Three-phase three-wire,
Δ Delta-connection, 2 CT, No PT
Three-phase four-wire,
Y-connection, 1 CT, 3 PT
Three-phase three-wire,
Δ Delta-connection, 1 CT, No PT
Three-phase four-wire,
Y-connection, 3 CT, No PT
Three-phase three-wire,
Δ Delta-connection, 3 CT, 2 PT
Three-phase four-wire,
Y-connection, 1 CT, No PT
Rated voltage Line voltage: 35 ~ 600 VAC (L-L)
Phase voltage: 20 ~ 400 VAC (L-N)
Rated current 1A / 5A
Frequency 45~65 Hz
Measurement
categories CAT II
Alarm Selectable alarm parameters 12 sets
Max/Min 53/41 Max/Min, Time stamp
Power supply Range 85~264 VAC (Power Consumption ≦ 15VA)
100~300 VDC (Power Consumption ≦ 5W)
Frequency Frequency for power supply 50/60 Hz
Communication
Interface RS-485 Interface
MODBUS-RTU
Baud Rate 1200 / 2400 / 4800 / 9600 /
19200 / 38400 / 57600 / 115200 bps
Shell Dimensions (W x H x D) 118 * 77* 199 mm
IP Protection IP20

5
Display
Screen LCD
Backlight White
Communication
RS-485 MODBUS RTU
Baud Rate 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 57600 / 115200 bps
Electromagnetic compatibility
Electrostatic discharge IEC 61000-4-2:2008
Immunity to radiated fields IEC 61000-4-3:2006+A1:2007+A2:2010
Immunity to fast transients IEC 61000-4-4:2012
Immunity to impulse waves IEC 61000-4-5:2014+A1:2017
Conducted immunity IEC 61000-4-6:2013/COR1:2015
Immunity to magnetic fields IEC 61000-4-8:2009
Immunity to voltage dips IEC 61000-4-11:2004/A1:2017
Radiated emissions FCC part 15 subpart B Class A
Conducted emissions FCC part 15 subpart B Class A
Harmonics emissions EN 61000-3-2:2014
Flicker emissions EN 61000-3-3:2013
2.2 Communication Spec.
2.3 Operation Interface
Environment
Operating Temperature 0℃ ~ +60℃ (32 ℉ ~ 140 ℉ )
Storage Temperature - 10 ℃ ~ +70 ℃
(14 ℉ ~ 158 ℉ )
Relative Humidity 5~ 95 % RH Non-condensing
Altitude Below 2000 meters
A. Title F. DOWN key
B. Display area G. COM light
C. ENTER key H. POWER light
D. LEFT key I. LOGGING light
E. UP key J. TOU light
SUMMARY-1 A Main
VLLavg 0.0
VI0.000
A
Psum 0
WFreq 0.00
Hz
IMP 1.8kwh
A
B
C D E F
G
H
I
J
K

6
Button General Mode Setting
ENTER Menu Press to confirm; return to the
previous page
LEFT None Press for 2 seconds to return to the
previous page
UP Press to switch the
summary pages Select item or increase number
DOWN Press to switch the
summary pages Select item or decrease number
2.3.1 Menu Tree
UI tree: display
Indice
Altri manuali ADTEK Strumento di misura

ADTEK
ADTEK MWH-8W Manuale utente

ADTEK
ADTEK CS3S VA Manuale utente

ADTEK
ADTEK CS1 Series Manuale utente

ADTEK
ADTEK CPM-80 Series Manuale utente

ADTEK
ADTEK CPM-20 Series Manuale utente

ADTEK
ADTEK CPM-12D Manuale utente

ADTEK
ADTEK AEM-DRB Manuale utente

ADTEK
ADTEK CPM-10 Manuale utente

ADTEK
ADTEK CS2-PR Manuale utente

ADTEK
ADTEK CPM-12B Manuale utente

ADTEK
ADTEK MWH-10 Manuale utente

ADTEK
ADTEK MW-5 Manuale utente

ADTEK
ADTEK CS1-PR Manuale utente

ADTEK
ADTEK CS2-MC Manuale utente

ADTEK
ADTEK MWH-10A Manuale utente

ADTEK
ADTEK AFM-8A Manuale utente

ADTEK
ADTEK CM1 Series Manuale utente

ADTEK
ADTEK CS2-VA Manuale utente

ADTEK
ADTEK CS2-SG Manuale utente

ADTEK
ADTEK CM1-TC Manuale utente