flamco WMS 2-1 Manuale utente

WMS 2-1
ENG Installation and operating instructions
Translation of the original operating instructions ––––––––––– 2
DEU Montage-und Betriebanleitung
Orginalbetriebsanleitung ––––––––––––––––––––––––––––––– 22
NLD Installatie- en bedieningsinstructies
Vertaling van de oorspronkelijke gebruiksaanwijzing ––––––– 42
FRA Installation et mode d’emploi
Traduction de la notice d’utilisation originale –––––––––––––– 62

2
English (ENG) Installation and Operating Instructions
Table of contents
1. About this operating manual 3
1.1 Layout of warning notices 3
2. Safety 3
2.1 Intended use 3
2.2 Foreseeable misuse 3
2.3 Safe handling 4
2.4 Staffqualications 4
2.5 Modicationoftheproduct 4
2.6 Liability 4
3. Product description 5
3.1 Function 6
3.2 Operating modes 7
4. Technical data 8
4.1 Permit, approval, registration 10
5. Transport and storage 10
6. Assembly and commissioning 10
6.1 Installing the sensor 10
6.2 Installing the signaling unit 11
6.3 Electrical connection 13
6.4 Starting up the product 15
6.5 Functional check 16
7. Operation 17
8. Maintenance 17
8.1 Maintenance intervals 17
8.2 Maintenance activities 17
9. Malfunctions 18
10. Decommissioning and disposal 19
11. Warranty 19
12. Copyright 19
13. Customer satisfaction 19
14. Addresses 19
15. Notes 20
15.1 Registration documents 20
15.2 EC Declaration of Conformity 21
ENG Installationandoperatinginstructions
Translationof the original operating instructions (DEU)

3
ENG
1. About this operating manual
This manual is part of the product.
fRead this manual before using the product.
fKeep this manual during the product’s service life, and keep it at hand for future
reference.
fPass on the operating manual to any subsequent owner or user of the product.
1.1 Layout of warning notices
Warning word This indicates the type and source of danger.
fThis indicates measures for avoiding the danger.
Warning instructions exist in three stages:
Warning word Explanation
DANGER Imminent danger!
Failure to observe will result in death or serious injury.
WARNING Potential imminent danger!
Failure to observe may result in death or serious injury.
CAUTION Dangerous situation!
Failure to observe so may result in minor or moderate injury, or
damage to property.
2. Safety
2.1 Intended use
The low water level protection system (WMS) is exclusively designed for monitoring water
levels in heating systems according to EN 12828. Low water levels (lack of water) are
detected and reported. Any other use is unintended.
2.2 Foreseeable misuse
The low water level protection system (WMS) must not be used in the following cases:
• Water temperature above 120 °C
• Water pressure above 10 bar
• Welding work on the sensor
• Areas with a risk of explosion
Incaseofoperationinareaswithariskofexplosion,sparkscancauseexplosions,resor
explosions.

4
ENG:Installationandoperatinginstructions
Translationoftheoriginaloperatinginstructions
2.3 Safe handling
This product is constructed in line with the current state of art and the current state of
recognized safety/engineering rules. Each product is tested before delivery to verify its
function and safety.
fThis product must only be operated in perfect condition, taking into account the
operating instructions, normal rules and regulations, and the applicable safety
regulations and accident prevention regulations.
WARNING Severe burns or death caused by mains voltage (230 V AC, 50 Hz) in the
signaling unit.
fAvoid contact between the signaling unit and water.
fBefore opening the signaling unit, or before maintenance and cleaning, disconnect the
power supply and safeguard against switching back on.
fDo not tamper with the signaling unit.
WARNING Severe burns to the body, especially the face and hands, due to heating
water escaping or spraying out.
The water in heating systems is under high pressure and can reach temperatures up to
100 °C.
fDo not tamper with the sensor and heating system.
fBefore opening the sensor, allow the heating water to drain or cool.
CAUTION Permanent damage to the sensor due to high water temperature or high
water pressure in the sensor.
fNever exceed the maximum permissible water temperature; see Table 1, Page 9.
fNever exceed the maximum permissible water pressure in the sensor; see Table 1,
Page 9.
2.4 Staff qualications
Installation, commissioning, operation, maintenance, decommissioning and waste
disposalmayonlybeperformedbyspeciallytrained,qualiedpersonnel.
Electricalworkmustbeperformedbyaqualiedelectricianinaccordancewiththe
applicable rules and regulations.
2.5 Modication of the product
Unauthorizedmodicationoftheproductcancausemalfunctionsandisprohibitedfor
safety reasons.
2.6 Liability
The manufacturer assumes no liability and provides no warranty for damage or
consequential damage caused by failure to observe the technical instructions, manuals
and recommendations.
The manufacturer and the distributor are not liable for any costs or damages incurred by
the user or a third party through the use of this product, especially in case of unintended
use of the product, misuse or malfunctions of the power supply, malfunction of the

5
ENG
product or connected products. Neither the manufacturer nor the distribution company
assume any liability for unintended use. The manufacturer assumes no liability for printing
errors.
3. Product description
The low water level protection system (WMS) consists of a fail-safe, self-monitoring
signaling unit with periodic self-test and a sensor.
The signaling unit and sensor are connected by a two-wire signal cable of up to 10 m in
length.
The product combination detects and reports low water levels (lack of water).
Sensor
Thesensorconsistsofametallicelectrodehousing,attedplasticcaseandanelectrode
rod that pulls out about 12 to 13 mm for functional testing.
The sensor is available in two versions:
fSensor DN 20:
Angledelectrodehousingwithtwo(DN20)weldedtting
(Øi=20mm,Øa=26.5mm)
1Electrode rod
2Plastic housing
3Electrode housing
4Union nuts G1", size 40
5Flange seal 30 x 21 x 2
6WeldedttingØ26.5
(DN20)
Fig. 1: Sensor DN 20

6
ENG:Installationandoperatinginstructions
Translationoftheoriginaloperatinginstructions
Signaling unit
The signaling unit contains indicators and controls in an impact-resistant plastic housing,
as well as all electronic components for evaluating and converting the sensor signal into a
digital output signal. The output is a zero potential relay contact.
The signaling unit is available in two versions:
fSignaling unit WMS 2-1:
With integrated power failure interlock; that is, after a power failure, the signaling unit
must be released.
aGreen operation lamp
bTest button
cRed alarm lamp
d
Release button
eWithout function
Fig. 2: Signaling unit
Type Signaling unit Sensor Component marking
WMS 2-1 WMS 2-1 DN 20 TÜV.WBH.14-345
3.1 Function
The WMS monitors water levels in heating systems. If the water level drops below
minimum, the low water level protection system alerts.
The operating principle of the low water level protection system relies on the conductivity
oftheheatingwater.Ifthereisaowofwaterthroughthesensor,thelowwaterlevel
protectionsystemindicatessufcientsupplyofheatingwater.Ifthereisnoowofwater
through the sensor, the signaling unit immediately alerts.
Sensor
The sensor consists of an outer electrode and an inner movable electrode. The two
electrodes are connected via a two-core cable to the signaling unit. The signaling unit
constantly monitors the conductivity (electrical resistance) between the two electrodes.
The inner movable electrode can be moved about 12 to 13 mm upwards from the water

7
ENG
for testing. As a result, the contact with the water is interrupted simulating a lack of water.
The signaling unit immediately alerts. An integrated spring returns the inner electrode back
to the starting position.
Signaling unit
The signaling unit constantly monitors the conductance of the water or the electrical
resistance between the two electrodes of the sensor. If the measured conductance greater
than20µS,orthemeasuredresistanceislessthan50kΩthesignalingunitindicatesa
sufficient supply of heating water and an error-free sensor circuit. The red alarm lamp is
unlit.Iftheconductanceislessthan20µS,ortheresistanceisgreaterthan50kΩ,thisis
interpreted as a lack of water, wire break or defective sensor circuit. The red alarm lamp is
lit.
The WMS is designed to be fail-safe and self-monitoring. The electronics in the signaling
unit check the entire low water level protection system several times a second.
Errors in the sensor circuit and signaling unit are displayed as alarms. The low water level
protection system can only be released if the entire low water level protection system is
error-free, a sufficient power supply is available, and the water level is above the minimum;
i.e., the red alarm lamp is unlit and the built-in relay is energized.
The green power light is lit when the low water level protection system is supplied with
mains voltage. The test button allows a functional check which simulates an alarm
condition.
3.2 Operating modes
The WMS 2-1 has an internal power failure interlock; that is, after a power failure, the
signaling unit must be released via the “Release” button or via an external release contact

8
ENG:Installationandoperatinginstructions
Translationoftheoriginaloperatinginstructions
4. Technical data
Table 1: Technical data, sensors
Parameters DN 20
General data
Housing dimensions (W x H x D) 130 x 270 x 44 mm
Space requirement (W x H x D) 100 x 300 x 150 mm
Weight 0.8 kg
Electrode housing Brass
Electrode rod Steel type 316
Resistance Boiler water
Mechanical connection Weldedtting
Ø i = 20 mm, Ø a = 26.5 mm
Operating pressure Max. 10 bar
Connecting cable:
Standard length:
Max. length
H05RN-F, 2 x 1 mm²
1.5 m
10 m (shielded)
Sensor voltage Max. 12 V
Operating temperature range
Environment 0°Cto+55°C
Medium Max.120°C
Storage -10°Cto+60°C
Electrical safety
Degree of protection IP 54
Table2:Technicalspecications,signalingunit
Parameters Value
General data
Housing dimensions (W x H x D) 100 x 188 x 65 mm
Weight 0.7 kg
delay time Approximately 1 second by default
Connections 1 output relay (switch)
1 external releasing device
Operating temperature range
Environment 0°Cto+55°C

9
ENG
Parameters Value
Storage -10°Cto+60°C
Voltage supply
Rated voltage AC 230 V ± 10%, 50Hz
Rated power 5 VA
Power supply fuse T50mA
Switching capacity output relay (1
zero-potential double throw switch)
Max. 250 V, 2 A resistive load
Electrical safety
Electrical safety EN60730
Protection class II EN 60730
Degree of protection IP 40 EN 60529
Electromagnetic compatibility (EMC)
As per EN 61000-6-3 EN 61000-6-3
As per EN 61000-6-2 EN 61000-6-2
Cable glands on the signaling unit
The middle grommet can be replaced by an M20 cable
gland.
Threaded cable glands Cable diameter
M16 4,0-8,8mm
M20 8,0-12,5mm

10
ENG:Installationandoperatinginstructions
Translationoftheoriginaloperatinginstructions
Fig. 3: Signaling unit and installation frame for installation in control panels; on the right: panel cut-out
4.1 Permit, approval, registration
WMS corresponds to the VdTÜV Bulletin “Water Level 100" (Edition 02.2010), the EMC
Directive (2004/108/EC), the Low Voltage Directive (2006/95 / EC) and the Pressure
Equipment Directive (97/23/EC).
5. Transport and storage
CAUTION DAMAGE TO THE PRODUCT DURING TRANSPORT.
fDo not throw or drop the product.
fProtect against moisture, humidity, dirt and dust.
CAUTION DAMAGE TO THE PRODUCT DUE TO IMPROPER STORAGE.
fStore only in a clean and dry environment.
fStore products only within the acceptable temperature range.
6. Assembly and commissioning
RDo not install the signaling unit and sensor in areas with a risk of explosion.
6.1 Installing the sensor
fInstall the sensor in a connection line between the water and steam chambers on the
boiler or parallel to the supply line between the boiler and the circulation pump.
If the boiler already has threaded sockets for the sensor, install it there.
fThere must not be a circulation pump with check valve and/or a shut off valve
between the sensor and the boiler.
fIt must be impossible to shut off the pipe to the sensor; it must have an internal
diameter of 20 mm (¾").
fInstall the sensor in accordance with this operating manual and using the supplied
gaskets.