Gira One 5023 00 Manuale utente

Switching actuator / blind actuator 16 A Standard
Table of Contents
1 Safety instructions.............................................................................................................3
2 Device components...........................................................................................................3
3 Function ............................................................................................................................4
4 Operation ..........................................................................................................................5
5 Information for electrically skilled persons ........................................................................9
5.1 Mounting and electrical connection........................................................................ 9
5.2 Commissioning .................................................................................................... 11
6 Technical data.................................................................................................................12
7 Parameter list ..................................................................................................................13
8 Warranty..........................................................................................................................16
2 / 17
82402632 15.12.2022

1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual
fully.
Danger of electric shock on the SELV/PELV installation. Do not connect loads for
mains voltage and SELV/PELV together to the device.
For parallel connection of several motors to an output it is essential to observe the
corresponding instructions of the manufacturers, and to use a cut-off relay if neces-
sary. The motors may be destroyed.
Use only Venetian blind motors with mechanical or electronic limit switches. Check
the limit switches for correct mastering. Observe the specifications of the motor man-
ufacturers. Device can be damaged.
Do not connect any three-phase motors. Device can be damaged.
This manual is an integral part of the product, and must remain with the end cus-
tomer.
2 Device components
Image1: Device components
(1) Button field for manual operation
(2) Programming button and LED
(3) Bus connection
(4) Status LEDs for outputs
(5) Load connections (relay outputs)
3 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

3 Function
System information
This device is a product for the Gira One Smart Home system. The Gira One system
is commissioned easily and in a time-saving manner using the Gira Project Assistant.
The Gira One Smart Home system enables the control and automation of lighting,
heating and shading, as well as connection to various third-party systems and much
more. It can be operated via Gira One switches, by app from home or securely from a
remote location. Electrically skilled persons can maintain the Gira One project re-
motely free of charge.
Data transmission between the Gira One devices is encrypted. This provides protec-
tion against third-party access and manipulation.
Commissioning is carried out with the free Gira Project Assistant (GPA), version 5 or
higher. Free function and security updates are also transferred to the Gira One
devices with the GPA.
The Gira One system is based on the globally proven KNX smart home standard.
Intended use
– Switching of electrical loads with potential-free contacts
– Switching of electrically-driven Venetian blinds, roller shutters, awnings and
similar hangings
– Installation in sub-distribution unit on DIN rail according to DIN EN 60715
– Operation in Gira One system
Product characteristics
– Outputs can be operated manually, construction site mode
– Manual switching between Venetian blind operation and switching operation
without commissioning
– Programming and commissioning with the Gira Project Assistant (GPA), ver-
sion 5 or higher.
– Updating via the Gira Project Assistant (GPA).
– Encrypted data transmission between the Gira One devices.
Characteristics switch operation
– Operation as NO or NC contacts
– Setting of a switch-on or switch-off delay.
– Staircase function for which a pre-warning time can additionally be set.
– Configuration as a switching function, e.g. for a light or sockets, as a garage
door function or door opener function, and as a potential-free switching contact
for transmission of the heat requirement to a heat pump.
– Garage door function: The time for closing the relay can be configured.
4 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

– Door opener function: The time for closing the relay can be configured.
Characteristics Venetian blinds operation
– Suitable for AC motors 110...230 V
– Control of blinds with slats, shutters, awnings, roof windows or roof domes.
– Travelling times can optionally be set.
– Sun protection function with blind or slat positions at the beginning and at the
end of the function can be set separately for each output.
– Setting of the delay time at the beginning or end of sunshine.
– Fabric stretching for awnings.
– If a wind alarm is active (e.g. as the result of an analogue wind sensor), the
Venetian blinds are raised and automatically locked. The status of the binary
input connected to the wind sensor is monitored cyclically.
– If a rain alarm is active (e.g. as the result of an analogue rain sensor), roof
windows or roof domes are closed and automatically locked. The status of the
binary input connected to the rain sensor is monitored cyclically.
– If a frost alarm is active (e.g. as the result of an analogue frost sensor), active
movements of shutters are stopped and disabled to protect the shutter motor.
The status of the binary input connected to the rain sensor is monitored cyclic-
ally.
– Door contact polling and visualisation in the Smart Home app: An open door
leads to the Venetian blind or shutters being raised and locked.
4 Operation
Image2: Operating elements
(4) Status LEDs for outputs
ON: Relay output closed
OFF: Relay output opened
Flashes slowly: Output in manual mode selected
Flashes quickly: Output disabled via continuous manual mode
(6) Button ǃ
Manual operation
5 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

(7) LED ǃ
ON: Continuous manual mode active/Flashing: Temporary manual mode
active
(8) LED DŽ
ON: Relay outputs closed, manual mode active
(9) Button DŽ
Short: Switch on, adjust slats or stop
Long: Move hanging upwards
(10) Button Dž
Short: Switch off, adjust slats or stop
Long: Move hanging downwards
(11) LED Dž
ON: Relay outputs opened, manual mode active
(12) Button ALL OFF
Open all relay outputs, stop drives
In operation with the button field the device distinguishes between a short and a long
press.
– Short: Pressing for less than 1 s
– Long: Pressing for between 1 and 5 s
In switching operation, the device distinguishes between the "NO contact" and
"NC contact" operating modes. The buttons (9 + 10) switch the switching state
when actuated:
NO contact: Switch on = close relay, Switch off = open relay
NC contact: Switch on = open relay, Switch off = close relay
The LED (4 + 8 + 11) always indicate the relay state.
Operating modes
– Bus operation: operation via push-button sensors or other bus devices
– Temporary manual control: manual control locally with keypad, automatic re-
turn to bus control
– Continuous manual mode: exclusively manual operation on the device
No bus operation is possible in manual mode.
After a bus failure and restoration the device switches to bus operation.
Switching on temporary manual operation mode
Operation is not disabled.
■ Press button ǃ (6) briefly.
LED ǃ (7) flashes, LEDs A1... (4) of the first configured output or output pair
flash.
Short-time manual operation is switched on.
6 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

After 5 s without a button actuation, the actuator returns automatically to bus
operation.
Switching off temporary manual operation mode
The device is in short-term manual mode.
■ No button-press for 5 s.
- or -
■ Press ǃ (6) button briefly as many time as necessary until the actuator
leaves the short-time manual mode.
Status LEDs A1... (4) no longer flash, but rather indicate the relay status.
Short-time manual operation is switched off.
Switching outputs: depending on the programming, the output relays switch to
the position that is active after the manual mode is switched off.
Venetian blind outputs: depending on the programming, the blind moves to the
position that is active after the manual mode is switched off, e.g. to safety or
sun protection position.
Switching on permanent manual operation mode
Operation is not disabled.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) lights up, LEDs A1... (4) of the first configured output or output
pair flash.
Continuous manual mode is switched on.
Switching off permanent manual operation mode
The device is in continuous manual mode.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) is off.
Continuous manual mode is switched off. Bus operation is switched on.
Switching outputs: depending on the programming, the output relays switch to
the position that is active after the manual mode is switched off.
Venetian blind outputs: depending on the programming, the blind moves to the
position that is active after the manual mode is switched off, e.g. to safety or
sun protection position.
Operating an output in manual mode
■ Activate short-term or permanent manual operation.
7 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

■ Press button ǃ (6) repeatedly until LED A1... (4) of the desired output or
output pair flashes.
■ Press button DŽ (9) or Dž (10).
Short: Switch on/off, drive stop.
Long: Move blind/shutter upwards/downwards.
LED DŽ (8) ON: Relay output closed
LED Dž (7) OFF: Relay output opened
Short-term manual mode: After running through all of the outputs the device
exits manual mode after another brief actuation.
Switching off all outputs / Stopping all hangings
The device is in permanent manual operation mode.
■ Press the ALL OFF button (12).
Switching outputs: all outputs switch off (NO operating mode: relay output
opened/NC operating mode: relay output closed).
Venetian blind outputs: all blinds/shutters stop.
Disabling outputs
The device is in continuous manual mode.
■ Press button ǃ (6) repeatedly until LED A1... (4) of the desired output or
output pair flashes.
■ Press the DŽ (9) and Dž (10) buttons simultaneously for approx. 5 s.
Selected output is disabled.
The status LED A1... (4) of the selected output or output pair flashes quickly.
A disabled output can be operated in manual mode.
Re-enabling outputs
The device is in continuous manual mode. One or more outputs were disabled in
manual mode.
■ Press button ǃ (6) repeatedly until the output to be unlocked or the output
pair is selected.
■ Press the DŽ (9) and Dž (10) buttons simultaneously for approx. 5 s.
Disabling is deactivated.
The LED A1... (4) of the selected output or output pair flashes slowly.
Switching between Venetian blind and switching operation
Device is not in operation
■ Activate permanent manual operation.
8 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

■ Press button ǃ (1) repeatedly until LED A1... (8) of the desired output or
output pair flashes.
■ Press the ǃ (1) and DŽ (4) and Dž (5) buttons simultaneously for
approx. 5 s.
Switching operation: Both status LEDs A1... (8) of the output pair light up.
Venetian blind operation: Both status LEDs A1... (8) of the output pair flash al-
ternately.
■ Press the DŽ (4) and Dž (5) buttons simultaneously.
Outputs switch between switching operation and Venetian blind operation.
Both status LEDs A1... (8) indicate the current operating mode.
■ Press the ǃ (1) and DŽ (4) and Dž (5) buttons simultaneously for
approx. 5 s.
Operating mode switchover is terminated, permanent manual operation mode
is activated.
■ Press the ǃ button (1) for approx. 5 s.
Operating mode switchover is terminated, permanent manual operation mode
is deactivated.
5 Information for electrically skilled persons
DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
5.1 Mounting and electrical connection
Mounting the device
– Enter or scan the device certificate and add it to the project. A high resolution
camera should be used to scan the QR code.
– The device certificate should be removed from the device during mounting.
– Document all passwords and keep them safe.
Observe ambient temperature. Ensure adequate cooling.
■ Mount device on DIN rail.
9 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

Connecting the device
Image3: Device connection (connection example)
■ Connect bus line with device connection terminal observing the correct polar-
ity.
■ Attach the cover cap to the bus connection as protection against hazardous
voltages.
■ Connect load as shown in the connection example. Two adjacent relay outputs
form a Venetian blind output.
The total current capacity of neighbouring outputs is a maximum of 20 A.
Image4: Total current capacity of neighbouring outputs
10 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard
Questo manuale è adatto per i seguenti modelli
2
Indice
Altri manuali Gira Controllori

Gira
Gira 1289 00 Manuale utente

Gira
Gira 0425 00 Manuale utente

Gira
Gira 0309 00 Manuale utente

Gira
Gira KNX 5062 00 Manuale utente

Gira
Gira 0399 00 Manuale utente

Gira
Gira 0566 Series Manuale utente

Gira
Gira System 3000 Manuale utente

Gira
Gira 2164 00 Manuale utente

Gira
Gira G1 Manuale utente

Gira
Gira 5023 00 Manuale utente

Gira
Gira 2114 00 Manuale utente

Gira
Gira One 5062 00 Manuale utente

Gira
Gira 5423 00 Manuale utente

Gira
Gira KNX 5061 00 Manuale utente

Gira
Gira KNX 1039 00 Manuale utente

Gira
Gira One Manuale utente

Gira
Gira 0388 00 Manuale utente

Gira
Gira KNX 2139 00 Manuale dell'operatore

Gira
Gira KNX 213900 Manuale utente

Gira
Gira 2100 Series Manuale utente