Rish OPTIMA VAF Manuale utente

RISH OPTIMA VAF
Operating Manual
2-60-006-00-00511_Rev. B - 9/2023

Installation & Operating Instructions
DIGITAL MULTIFUNCTION INSTRUMENT
Programmable Multi-function Digital Panel Meter
Section Contents
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.2 Set Up Screens
3.2.1 System Type
3.2.2 Potential Transformer Primary value
3.2.3 Current Transformer Primary value
3.2.4 Potential Transformer Secondary value
3.2.5 Current Transformer Secondary value
3.2.6 Reset
3.2.7 Auto Scrolling
3.2.8 Number of poles
3.2.9 Relay Limit Parameter (Optional)
2

6. Optional Pluggable Module
4. Installation
4.1 EMC Installation Requirements
4.2 Case Dimensions and Panel Cut-out
4.3 Wiring
4.4 Auxiliary Supply
4.5 Fusing
4.6 Earth / Ground Connections
5. Connection Diagrams
Specification
7.
3

TABLE 1: Measured Parameters System Wise:
Measured Parameters
System Voltage
System Current
Frequency
Voltage VL1-N / VL2-N / VL3-N
Voltage VL1-L2 / VL2-L3 / VL3-L1
Current L1 / L2 / L3
Units
Volts
Amps
Hz
Volts
Volts
Volts
Run Hour
On Hour
Number of Interruptions
Hours
Hours
Counts
3P 4W 3P 3W 1P 2W
üü
üü
ü
ü
û
û
ü
ü
ü
üü
üüû
ü
ü ü ü
üüü
üü ü
û
Min / Max System Voltage
Min / Max System Current
Volts
Amps
ü
ü
ü ü
üü
1. INTRODUCTION
The VAF is a panel mounted 96 x 96mm DIN Quadratic Digital Panel Meter for the measurement of
important electrical parameters like AC Voltage, AC Current, RPM, Frequency.
The instrument integrates accurate measurement technology (All Voltages & current measurements
are True RMS upto 15th Harmonic) with 3 line 3 digits Ultra high bright LED display.
VAF can be congured and Programmed On site for the following :
PT Primary, PT Secondary, CT Primary, CT Secondary (5A or 1A)
and System Type 3 phase 3W or 4W or single phase system.
The front panel has two push buttons using which the user can scroll
through different screens and congure the product.
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
UP
DOWN
2. MEASUREMENT READING SCREENS
In normal operation, the user is presented with one of the measurement reading screens out of
several screens. These screens may be scrolled through one at a time in incremental order by
pressing the “UP key” and in decremental order by pressing “DOWN key”.
4

3. Programming
3.1. Password Protection
The following sections comprise step by step procedures for conguring the VAF for individual user
requirements. To access the set-up screens press and hold the “DOWN” and “UP” keys
Simultaneously. This will take the User into the Password Entry screen (Section 3.1).
In Setup mode, if none of the key pressed within 1 min, it will returns operation to the measurement
mode.
Password protection can be enabled to prevent unauthorized access to set-up screens, by default
password protection is not enabled.
Password protection is enabled by selecting a three digit number other than 000,setting a password
of 000 disables the password protection.
Enter Password, prompt for rst digit.
(* Denotes that decimal point will be ashing).
Press the “DOWN” key to scroll the value of the rst digit from 0 through
to 9, the value will wrap from 9 round to 0.
Press the “UP” key to advance to next digit.
In the special case where the Password is “000” pressing the “UP” key
when prompted for the rst digit will advance to the “Password
Conrmed” screen.
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
*
5

Enter Password, third digit entered, Awaiting verication of password.
Password conrmed.
Pressing “V” key will advance to the “New / change Password” entry
stage.
Pressing the “UP” key will advance to the system type edit screen. (See
section 3.2).
Enter Password, rst digit entered, prompt for second digit.(* Denotes
that decimal point will be ashing).
Press the “DOWN” key to scroll the value of the second digit from 0
through to 9, the value will wrap from 9 round to 0.
Press the “UP” key to advance to next digit.
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
*
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
*
Enter Password, second digit entered, prompt for third digit.(* Denotes
that decimal point will be ashing).
Press the “DOWN” key to scroll the value of the third digit from 0 through
to 9, the value will wrap from 9 round to 0.
Press the “UP” key to advance to password conrmation screen.
6

New / Change Password, rst digit entered, prompting for second
digit.(*Decimal point indicates that this will be ashing).
Pressing the “DOWN” key will scroll the value of second digit from 0
through to 9, the value will wrap from 9 round to 0.
Pressing the “UP” key to advance the operation to the Next digit and
sets the rst digit, in this case to “5”
Password Incorrect.
The unit has not accepted the Password entered.
Pressing the “DOWN” key will return to the Enter Password stage.
Pressing the “UP”key exits the Password menu and returns operation to
the measurement reading mode.
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
New / Change Password
(*Decimal point indicates that this will be ashing).
Pressing the “DOWN” key will scroll the value of the rst Digit from 0
through to 9, the value will wrap from 9 round to 0.
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
*
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
*
7

This screen is used to edit and set the system type. System type ”3” for 3
phase 3 wire & “4” for 3 phase 4 wire & 1 for Single phase system.
Pressing “UP” key accepts present value and advances to the “Potential
transformer Primary Value Edit” menu.
Pressing “DOWN” Key will enter the System type edit mode.
New / Change Password, second digit entered, prompting for third digit.
(*decimal point indicates that this will be ashing).
Pressing the “DOWN” key will scroll the value of the third from 0 through
to 9, the value will wrap from 9 round to 0.
Pressing the “UP” key to advance the operation to “New Password
Conrmed” and sets the third digit, in this case to “7”.
New Password conrmed.
Pressing the “DOWN” key will return to the “New/Change Password”.
Pressing the “UP” key will advances to the Set up screen.(see section
3.2).
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
3.2 Set Up Screens
3.2.1. System Type
*
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
8

PT ratios, the values displayed represent the voltage.
Pressing the “UP” key accepts the present value and advances to the
“Current Transformer Primary value Edit” menu. (See Section 3.2.3)
Pressing the “DOWN” key will enter the “Potential transformer Primary
value edit mode.
System Type Edit
This screen appears only if “DOWN” key is pressed in previous Menu.
Pressing “DOWN” scrolls through the values available.
Pressing “UP” Key advances to the system type Conrmation menu.
3.2.2. Potential Transformer Primary Value
System Type Conrmation
This screen will only appear following the edit of system type.
Pressing the “UP” key set the displayed value as system Type and will
advance to “Potential Transformer Primary Value Edit” menu. (See
section 3.2.2)
The nominal full scale voltage which will be displayed as the Line to Line voltage for all system types.
This screen enables the user to display Line to Line and Line to neutral Voltages inclusive of any
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
9

Note : The ashing decimal point indicates the cursor position, a steady decimal point will be present
to identify the scaling of the number until the cursor position coincides with the steady decimal point
position. At this stage the decimal point will ash.
When the least signicant digit has been set, pressing the “UP” key will advance to the “Potential
transformer Primary Value Conrmation” stage.
Potential Transformer Primary Digit Edit
Pressing the “DOWN” key will scroll the value of the most signicant digit
from 0 to 9 unless the presently displayed Potential Transformer Primary
value is less than 799 kilovolts in that case the digit range will be
restricted.
Pressing the “UP” key accepts the present value at the cursor position
and advances the cursor to the next Less signicant digit.
Initially the PT value must be selected pressing the “DOWN” key will move the decimal point position
to the right side until it reaches # # #. after which it will return to #. # # with x1000 annunciation.
Pressing the “UP” key accepts the present multiplier (Decimal Point position ) with x1000 annunciation
and advances to the “Potential Transformer Primary Digit Edit” Screen.
Note : PT Values must be set as Line to Line Voltage for Primary as well as Secondary for all
system types (3P3W/3P4W/1P2W).
*
L3-L1
L2-L3
Hz x1000
L1-L2
Volt x1000
L3
L1
L2 Ax1000
10