1) Visu Cycle:
In this position, the CYCLE menu led is on fixe.
If a fault is present, display of the fault (this display has priority).
If the sequencer is stopped: display "0".
If an unclogging pulse is in progress:
- display of "n x" with x = number of the current SV
- rapid flashing of the menu led in front of T1.
If rest time between two shots in progress:
- display of the time count before the next pulse
- rapid flashing of the menu led in front of T2.
Whether it is an unclogging of n cycles in manual operation, or unclogging due to the detection of a
fan stop, rapid flashing of the menu led in front of the fan / manual
At any time, if the + key is pressed: display of "n x" with x = EV which will be engaged on the next shot.
2) Setting the stop mode:
Two stop modes are possible if loss of loop control (input I1):
- « FcY » for end of cycle: the current cycle ends until the last SV.
- « Sto » for cycle stop: the cycle stops at the EV where it arrived. It will resume at the next EV when
reappearance of the run order
3) Setting the number of outputs:
Number of SV in the cleaning cycle: from 1 to 18.
4) T1 setting:
Activation time of an output (in 1 / 100th of a second) : from 3 to 255.
5) T2 setting:
Idle time between two outputs (in seconds) : from 1 to 255.
6) T4 setting:
If there has been no unclogging for the set time (T4), the current cycle ends (if stopped in cycle)
and a full cycle is performed.
If set to 0: this function is disabled.
Note: the T4 time delay is initialized for each pulse on an SV.
7) Setting the number of cycles when the fan is stopped:
If the loop control is lost (input I1), the stopping of the fan is detected.
In this case, the n cleaning cycles set here are carried out one after the other.
If set to 0: this function is disabled.
8) Manual running:
Setting the desired number of cycles in manual running. The cleaning cycles follow one after the other
(regardless of the state of input I1).