Manual ver 2.0 10
Connection for the extensiometric
gauge input
3.2 Configuration of the different inputs
Each instrument is default configured for a type J input (Fe-
CuNi). It is possible to change the set-up of the type of input simply with
the INP parameter from the menu. In the AK32, the second channel
always shows the reading of the pressure transducer.
INP
Value
Meaning
0 J : 0..600°C (Fe-CuNi, IEC584)
1 L : 0..600°C (Fe-CuNi, DIN43710)
2 K: 0..1200°C (NiCr-NiAl, IEC584)
3 N: 0..1200°C (NiCrSi-NiSi, IEC584)
4 T: 0..400°C (Cu-CuNi, IEC584)
5 R: 0..1600°C (Pt/13%Rh-Pt, IEC584)
6 S: 0..1600°C (Pt/10%Rh-Pt, IEC584)
7 RTD, Pt100: -200..600°C (IEC751)
8 RTD, Pt100: -99,9..200,0°C (IEC751)
9 Voltage V DC 0..5 V (Impedance >1 Mohm)
10 Voltage V DC 0..10 V (Impedance >1 Mohm)
11 Current loop 0..20 mA (load 150 ohm)
12 Current loop 4..20 mA (load 150 ohm)
13 Pressure transducer ( only AK30 )
14 Extensiometric gauge 350 ohm( only AK30 )