Ver.1.0
When hold FUNC button for 10 seconds while on Menu Mode, Advanced menu will be shown. If
paramemters are locked, a password will be required
Symbol Name Meaning
Input type tc-J: thermocouple J (0..600ºC)
tc-L: thermocouple L (0..600ºC)
tc-K: thermocouple K (0..1200ºC)
tc-N: thermocouple N (0..1200ºC)
tc-t: thermocouple T (0..400ºC)
tc-r: thermocouple R (0.1600ºC)
tc-S: thermocouple S (0..1600ºC)
Rtd1: Pt100 (-200..600)
Rtd2: Pt100 (-99,9..200,0)
If temperature is over the specified maximum range,
temperature display will show Over. If temperature is under
minimum range, display will show Under
Unit ºC: celsius degree
F: Farenheit degree
Heat Off: Output PID control is direct
On: output PID control is reverse
Alarm Setup Off: Alarm is disabled
Hi: Alarm is an absolute high alarm (alarm active if temperature
higher than Alarm Absolute Setpoint)
Lo: Alarm is an absolute low alarm (alarm active if temperature
lower than Alarm Absolute Setpoint)
rHi: Alarm is an relative high alarm (alarm active if temperature
higher than current setpoint + Alarm Relative Setpoint)
rHi: Alarm is an relative low alarm (alarm active if temperature
lower than current setpoint + Alarm Relative Setpoint)
Wnd:Alarm is a windowed alarm (alarm is active if temperature
is outside the margin (current setpoint- Alarm Relative
Setpoint, current setpoint+Alarm Relative Setpoint)
Latched Alarm Off: Do nothing
On: Once alarm is set active, it remains in active status until it
is reset using "Reset Alarm Status"
Additional details: Shown if "Alarm Setup" is not Off
Masked Alarm Off: Do nothing
On: If on startup or setpoint change alarm status is active,
controller mask it until it gets to an inactive condition. Once
alarm is incactive mask is removed
Additional details: Shown if "Alarm Setup" is not Off
Alarm Direction reV: alarm contact open on active alarm
dir: alarm contact closed on active alarm
Additional details: Shown if "Alarm Setup" is not Off
Show Alarm On Operation Off: Alarm parameters are shown on advanced menu
On: Alarm parameters are shown on normal menu
Alarm Absolute Setpoint Temperature value used to activate/deactivate alarm status
Limited by selected input type
Additional details: Shown if "Alarm Setup" is Hi or Lo and
"Show Alarm On Operation" is Off
Cannot be changed if parameters are locked