Strider M72 ME-PM-M72
5. Unit Characteristics
The Unit can measure and display:
The unit has password-protected set-up screens for:
• Line voltage and THD% (total harmonic distortion) of all phases
• 2~63rd voltage IHD% (Individual Harmonic distortion) of all phases
• Line Frequency
• Phase Sequence
• Currents, Current demands and current THD% of all phases
• 2~63rd current IHD% of all phases
• Active power, reactive power, apparent power, maximum power demand and power factor
• Max./ Min.Current and voltage, Max.current demand
• Import / export / total active energy
• Import / export / total reactive energy
• Total active energy of each phase
• DPF ( Displacement Power factor, Modbus read only)
• Voltage crest factor (Modbus read only)
• Current K factor (Modbus read only)
• Communication setting: Modbus address, Baud rate, Parity, Stop bit
• CT setting: CT 1 ( Primary) , CT2 ( locked .333V), CT rate
• PT setting: PT1 (Primary), PT2 (Secondary) , PT rate
• Demand setting: demand method, Demand interval time
• Time setting: Backlit time, display scroll time, system RTC.
• System conguration: System type, System connect, Change password, Auto display scroll
• Reset: Energy, Demand, Max.Min value.
CT and PT
RS485 Serial-Modbus RTU
CT1 (primary current): 1~9999A
CT2 (secondary current): 333mV
PT1 (primary voltage): 100V ~ 500,000V
PT2 (secondary voltage): 100 to 480 V AC (L-L)
This unit uses a RS485 serial port with Modbus RTU protocol to provide a means of remote monitoring and controlling.
Please check the Part 4.2 for the details of setting.
Display
Liquid crystal display with backlit (360o full viewing angles)
4 lines, 4 digits per line to show electrical parameters
5th line, 8 digits to show energy
Bar graph for power indication
Display update time: 1 sec. for all parameters
Display scrolling: automatic or manual (Programmable)